Controlling Additional Fixtures With Your JourneyMan®
Replacement Motion Sensor
❒When wiring to additional standard fix- tures: Connect the sensor's red wire to the standard light's black wires. Connect all white wires together. Total fixture ratings must not exceed 1000W (8.3 A).
NOTE: All wiring between fixtures should be run in accordance with the National Electrical Code through conduit or another acceptable means.
Contact a qualified electrician if there is any question as to the suitability of the system.
❒This sensor has a rating of 1000W. If your fix- ture is only rated 300W, 700W of additional load may be controlled by this sensor.
❒When determining what a fixture is rated for, do not simply look at the rating on the lamp in the fixture. Look at the marking which speci- fies the maximum lamp wattage for which the fixture is suitable.
❒Once you have selected the fixtures to be con- nected and determined their maximum ratings, add these ratings up. For instance, if you have 3 fixtures rated 100W, 150W, and 75W respec- tively, you have a total load of 325W.
|
|
|
|
| BLACK from Switch |
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
| to BLACK from |
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
| JourneyMan® | RED from |
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| JourneyMan® to |
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| BLACK from Fixture |
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
WHITE from Line | WHITE from Line |
|
to WHITE from | to WHITE from | (Standard) |
JourneyMan® | Fixture |