INSTALLATION

Mantel Clearances Floor Clearances

9

INSTALLATION

Continued

MANTEL CLEARANCES

In addition to meeting noncombustible material clearances, you must also meet required clearances between fireplace opening and mantel shelf.Ifyoudonotmeettheclearanceslistedbelow,youwillneedahood.

Determining Minimum Mantel Clearance

If you meet minimum clearance between mantel shelf and top of fireplace opening, a hood is not required (see Figure 6).

Determining Minimum Mantel Clearance When Using a Hood

If minimum clearances in Figure 6 are not met, you must have a hood. When using a hood there are still certain minimum

10"

8"

6"

2 1/2"

Minimum Non-

 

 

(A)

 

Combustible

 

Material

12"

 

 

 

 

 

 

8"

 

 

 

 

Mantel Shelf

18"

 

20"

22"

 

14"

 

17"

19"

 

 

 

 

Underside of

Mantel Shelf

All minimum distances are in inches

Log Set

24" 24"/30" Models

20" 18" Model

Top of Fireplace

Opening

mantel clearances required. Follow minimum clearances shown in Figure 7 when using hood.

NOTICE: Surface temperatures of adjacent walls and mantels become hot during operation. Walls and mantels above the firebox may become hot to the touch. If installed properly, these temperatures meet the requirement of the national product standard.

Minimum Non-

Distances to

Combustible

Underside of

Material Height

Mantel

Figure 6 - Minimum Mantel Clearances Without Using Hood

Follow all minimum clearances shown in this manual.

NOTICE: If your installation does not meet the minimum clearances shown, you must do one of the following:

operate the logs only with the flue damper open

raise the mantel to an acceptable height

remove the mantel

FLOOR CLEARANCES

A.If installing appliance on the floor level, you must maintain the minimum distance of 14" to combustibles (see Figure 8).

B.If combustible materials are less than 14" to the fireplace, you must install appliance at least 5" above the combustible floor- ing (see Figure 9).

Minimum Non-

Combustible

Material

Mantel Shelf

12"

Underside of

10"

 

 

 

 

 

Mantel Shelf

 

 

 

 

 

 

8"

 

 

 

 

 

 

 

6"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 1/2"

 

 

 

 

 

All minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

distances are

 

 

 

 

 

 

in inches

 

 

 

 

 

 

 

Log Sets

 

8"

12"

15"

18"

20"

 

18", 24",

 

 

Min.

 

 

 

 

 

& 30" Models

 

 

 

 

 

 

 

 

 

Top of Fireplace

 

Opening

Hood

Distances to

(GA6050, GA6052,

Underside of

or GA6053)

Mantel

 

Figure 7 - Minimum Mantel Clearances When Using Hood

 

Combustible

 

14"

Material

 

 

 

Min.

 

Hearth

 

 

Combustible

 

 

Material

 

Noncombustible

5"

 

Min.

 

Material

 

 

Figure 8 - Minimum Fireplace

Figure 9 - Minimum Fireplace

Clearances If Installed at Floor

Clearances Above

Level

 

Combustible Flooring

For morevisit www..com

104415-01H

Page 9
Image 9
Desa R installation manual Mantel Clearances, Floor Clearances, Determining Minimum Mantel Clearance

R specifications

Desa R is an innovative urban development designed as a model for sustainable living. Located in a prime setting, it combines modern technology with an eco-friendly approach, making it a standout community in today's urban landscape. The main features of Desa R revolve around sustainability, community engagement, and smart city solutions.

One of the cornerstones of Desa R is its commitment to sustainability. The development incorporates extensive green spaces, which not only promote biodiversity but also provide residents with recreational areas. Parks, gardens, and tree-lined streets are thoughtfully distributed throughout the area, encouraging outdoor activities and community gatherings. The design emphasizes walkability, reducing the need for vehicular transportation and promoting healthier lifestyles.

Desa R utilizes advanced technologies to enhance the living experience. Smart home systems are integrated into residential units, allowing for control of lighting, heating, and security through mobile applications. This technology not only contributes to energy efficiency but also provides residents with convenience and peace of mind. Additionally, smart waste management systems are in place, utilizing sensors to optimize waste collection routes and minimize environmental impact.

The development also prioritizes renewable energy sources. Solar panels are installed on rooftops, harnessing sunlight to provide clean energy for homes and shared facilities. This not only reduces energy costs for residents but also contributes to the community's overall carbon footprint reduction.

Community engagement is another integral aspect of Desa R. A variety of communal spaces, such as coworking hubs, community centers, and event venues, facilitate social interaction and collaboration among residents. Regular workshops and events are organized to foster a sense of belonging and encourage skill-sharing among community members.

Transport in Desa R is designed to be efficient and sustainable as well. The area is well-connected with public transport options, including electric buses and cycling paths, making it easier for residents to travel without relying heavily on personal vehicles.

In summary, Desa R embodies the future of urban living, characterized by sustainability, technological integration, and community-oriented design. It serves as a blueprint for future urban developments, demonstrating that modern living can harmonize with the environment and foster strong community ties.