AIR FOR COMBUSTION AND VENTILATION
Determining
5
AIR FOR COMBUSTION AND VENTILATION
Continued
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or uncon- fined space.
Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.
1.Determine the volume of the space (length x width x height). Length x Width x Height = cu. ft. (volume of space)
Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.
2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
(volume of space) x 20 = (maximum Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)
3.Add the Btu/Hr of all fuel burning appliances in the space.
______________ | Btu/Hr | |
Gas water heater* | ______________ Btu/Hr | |
Gas furnace | ______________ Btu/Hr | |
Vented gas heater | ______________ Btu/Hr | |
Gas fireplace logs | ______________ | Btu/Hr |
A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.
B.Vent room directly to the outdoors. See Ventilation Air From Out- doors, page 6.
C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
WARNING: If the area in which the heater may be operated is smaller than that defined as an uncon- fined space or if the building is of unusually tight construction, provide adequate combustion and ven- tilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Sec- tion 5.3 or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.
Other gas appliances* + | _____________ | Btu/Hr | |
Total | = | _____________ | Btu/Hr |
*Do not include
Example: |
Ventilation
Grills
Into Adjoining
12"
Ventilation Grills Into Adjoining Room,
Gas water heater | 40,000 |
_____________ Btu/Hr |
Room,
Or
Option 2
Option 1
Remove
+ | 30,000 | |
_____________ Btu/Hr | ||
Total | = | 70,000 |
_____________ Btu/Hr |
4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
__________________ Btu/Hr (maximum the space can support)
__________________ Btu/Hr (actual amount of Btu/Hr used)
Example: 51,200 Btu/Hr (maximum the space can support) 70,000 Btu/Hr (actual amount of Btu/Hr used)
The space in the above example is a confined space because the actual Btu/ Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:
Door into Adjoining Room, Option 3
12"
Figure 2 - Ventilation Air from Inside Building
For morevisit www..com