FIREPLACE INSTALLATION

Installing Gas Piping to Fireplace Location (Cont.) Connecting Fireplace to Gas Supply Checking Gas Connections

19

FIREPLACE INSTALLATION

Continued

CAUTION: Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diam- eter or greater to allow proper gas volume to fireplace. If pipe is too small, undue loss of volume will occur.

Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure 31).

IMPORTANT: Install main gas valve (equipment shutoff valve) in an accessible location. The main gas valve is for turning on or shutting off the gas to the appliance.

Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fireplace valves.

WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

We recommend that you install a sediment trap/drip leg in supply line as shown in Figure 31. Locate sediment trap/drip leg where it is within reach for cleaning. Install in piping system between fuel supply and fireplace. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into fireplace gas con- trols. If sediment trap/drip leg is not installed or is installed wrong, fireplace may not run properly.

CSA Design-Certified

Equipment Shutoff Valve

with 1/8" NPT Tap*

CONNECTING FIREPLACE TO GAS SUPPLY

Installation Items Needed

5/16" hex socket wrench or nut-driver

sealant (resistant to propane/LP gas, not provided)

1.Open lower louver door panel by gently pulling forward.

2.Route flexible gas line (provided by installer) from equipment shutoff valve to fireplace. Route flexible gas supply line through one of the access holes on side of fireplace.

3.Attach flexible gas line from gas supply to control valve (see Figure 32).

4.Check all gas connections for leaks. See Checking Gas Connections.

To Gas Supply

(Natural)Equipment

Shutoff Valve

To External

Control Valve

Regulator

(Propane/LP)

 

Flexible Gas Line

Do NOT Kink

Figure 32 - Connecting Flexible Gas Line to Millivolt Valve

CHECKING GAS CONNECTIONS

Approved Flexible

Gas Line

3" Minimum

Natural - From Gas Meter (5.5" W.C. to 10.5"

W.C. Pressure)

Propane/LP From External Regulator (11" W.C. to 14" W.C. Pressure)

WARNING: Test all gas piping and connections , internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Cap Pipe Nipple Tee Joint

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

Figure 31 - Gas Connection

Sediment Trap/Drip Leg

1.Disconnect fireplace and its individual equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig (3.5 kPa) will damage fireplace gas regulator.

*The CSA design-certified equipment shutoff valve may be sup- plied with the appliance or you can purchase it from your retailer.

For morevisit www..com

111923-01B

Page 19
Image 19
Desa (V)K36P SERIES Connecting Fireplace to GAS Supply, Checking GAS Connections, Installation Items Needed

(V)K36P SERIES, (V)K36N SERIES specifications

Desa (V)K36P Series and (V)K36N Series represent a significant advancement in the world of high-efficiency heating solutions, known for their innovative features and technologies that cater to varying heating needs. These series are engineered for both residential and commercial applications, offering flexibility and efficiency to meet diverse climate requirements.

One of the standout features of the Desa (V)K36P and (V)K36N Series is their advanced combustion technology. Utilizing a unique burner design, these units maximize energy output while minimizing emissions. This is particularly important in today's environmentally-conscious market, where efficient energy use and reduced carbon footprints are critical.

Moreover, these series incorporate advanced heat exchanger technologies that ensure optimal thermal efficiency. This design minimizes heat loss and enhances the performance of the heating system, allowing users to enjoy comfortable indoor temperatures without excessive energy costs. The durable materials used in the construction of these heat exchangers also contribute to their longevity and reliability, making them a worthy investment.

Another notable characteristic of the Desa (V)K36P and (V)K36N Series is their user-friendly control systems. Features such as digital thermostats and programmable settings allow users to customize their heating schedules with ease, ensuring their living or working spaces remain comfortable at all times. Additionally, some models come equipped with Wi-Fi connectivity, enabling remote operation and monitoring via smartphone applications.

In terms of safety, the Desa series does not compromise. Each unit includes multiple safety features, such as overheat protection, flame failure detection, and pressure relief systems, ensuring that users can rely on their heaters with peace of mind.

Installation and maintenance are also made simpler with the Desa (V)K36P and (V)K36N Series. These models are designed for straightforward installation, minimizing disruptions during setup. They also require minimal maintenance, which reduces long-term service costs for users.

In conclusion, the Desa (V)K36P and (V)K36N Series stand out in the market due to their innovative technologies, high efficiency, user-friendly controls, and robust safety measures. These qualities make them excellent choices for anyone seeking reliable and effective heating solutions in a variety of settings.