Desa VP26TA VN30A Continued, Observed Problem, Possible Cause, Remedy, ODS/pilot lights but flame

Models: VN30TA VP16ITA VN18TA VP16A VP22ITA VP26A VP26TA VN30A VP16TA VN18A

1 36
Download 36 pages 38.6 Kb
Page 21
Image 21
ODS/pilot lights but flame

TROUBLESHOOTING

Continued

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

 

 

 

 

ODS/pilot lights but flame

1. Control knob not fully pressed in

1.

Press in control knob fully

goes out when control knob is

2. Control knob not pressed in

2. After ODS/pilot lights, keep con-

released

 

long enough

 

trol knob pressed in 30 seconds

 

3.

Equipment shutoff valve not

3.

Fully open equipment shutoff

 

 

fully open

 

valve

 

4.

Thermocouple connection

4.

Hand tighten until snug, then

 

 

loose at control valve

 

tighten 1/4 turn more

 

5.

Pilot flame not touching ther-

5.

A) Contact local natural or

 

 

mocouple, which allows ther-

 

propane/LP gas company

 

 

mocouple to cool, causing

 

B) Clean ODS/pilot (see

 

 

pilot flame to go out. This

 

Cleaning and Maintenance,

 

 

problem could be caused by

 

page 19) or replace ODS/pilot

 

 

one or both of the following:

 

assembly

 

 

A) Low gas pressure

 

 

 

 

B) Dirty or partially clogged

 

 

 

 

ODS/pilot

 

 

 

6.

Thermocouple damaged

6.

Replace pilot assembly

 

7.

Control valve damaged

7.

Replace control valve

 

8.

Safety interlock system has

8.

Wait one minute for safety in-

 

 

been triggered (thermostat

 

terlock system to reset. Repeat

 

 

models only)

 

ignition operation

 

 

 

 

Burner(s) does not light after

1. Burner orifice(s) is clogged

1.

Clean burner orifice(s) (see

ODS/pilot is lit

 

 

 

Cleaning and Maintenance,

 

 

 

 

page 19) or replace burner

 

 

 

 

orifice(s)

 

2.

Inlet gas pressure is too low

2.

Contact local natural or pro-

 

 

 

 

pane/LP gas company

 

 

 

 

Delayed ignition of burner(s)

1. Manifold pressure is too low

1.

Contact local natural or pro-

 

 

 

 

pane/LP gas company

 

2.

Burner orifice(s) is clogged

2.

Clean burner orifice(s) (see

 

 

 

 

Cleaning and Maintenance,

 

 

 

 

page 19) or replace burner

 

 

 

 

orifice(s)

 

 

 

 

Burner backfiring during com-

1. Burner orifice(s) is clogged or

1.

Clean burner orifice(s) (see

bustion

 

damaged

 

Cleaning and Maintenance,

 

 

 

 

page 19) or replace burner

 

 

 

 

orifice(s)

 

2.

Burner damaged

2.

Replace burner

 

3.

Gas regulator defective

3.

Replace gas regulator

 

 

 

 

Burner plaque(s) does not

1. Plaque damaged

1.

Replace burner

glow

2. Inlet gas pressure is too low

2.

Contact local natural or pro-

 

3.

Control knob set between

 

pane/LP gas company

 

3.

Turn control knob until it

 

 

locked positions

 

locks at desired setting

 

 

 

 

Slight smoke or odor during

1. Residues from manufacturing

1.

Problem will stop after a few

initial operation

 

processes

 

hours of operation

113052-01D