Desa CHDV47NR Horizontal Termination Configurations, Venting Installation Instructions, Continued

Models: CHDV47PR (V)V36N CHDV47NR

1 44
Download 44 pages 32.52 Kb
Page 10
Image 10
Horizontal Termination Configurations

10

VENTING INSTALLATION INSTRUCTIONS

Installation Planning (Cont.)

VENTING INSTALLATION INSTRUCTIONS

Continued

9.Slide wall firestop against interior wall surface and attach with screws provided. See Figure 13 for horizontal termination details.

10.Place fireplace into position and shim with noncombustible ma- terial if needed. Nail or screw side flanges to framing to secure unit in place. IMPORTANT: Make sure fireplace is level before securing. If fireplace is not level it will not work properly.

Manual background WARNING: Never run vent downward as this may cause excessive temperatures which could cause a fire. Operation of improperly installed and main- tained venting system could result in serious injury, property damage or loss of life.

Minimum Pipe

Siding Standoff

Overlap 11/4"

 

 

Screws

Direct Vent

 

Pipe

 

Wall

 

Firestop

 

Maintain 1"

 

Minimum Air

High Wind

Space Around

Outer Pipe When

Termination

Penetrating a Wall

 

 

Apply Mastic to

10 3/4" x 10 3/4"

Outside Edge of

Framed

Standoff

 

Opening

 

 

Exterior Wall

 

with Vinyl Siding

Figure 13 - Typical Horizontal Termination Cap Mounting with Additional Siding Standoff Installed

Horizontal Termination Configurations

Figures 14 through 18 show different configurations and alternatives for venting with horizontal termination. Each figure includes a chart with critical minimum and maximum dimensions which MUST be met. IMPORTANT: Remember that a horizontal run of venting must have a 1/4" rise for every 12" of run toward the termination.

GROUND FLOOR INSTALLATION

Recommended Applications:

Installation using cabinet surrounds

Through the wall using round or square termination (up to 12" horizontal pipe)

NOT FOR CORNER INSTALLATION

45° Elbow

Horizontal High

Wind Square

Termination

Adjustable

Pipe 12" Max.

Wall

Firestop

Square Termination

 

Vertical (V)

Horizontal (H)

V36 Series

35" min.

17" max.

V42 Series

39" min.

17" max.

CHDV Series

39" min.

17" max.

45° Elbow

Exterior Portion of Wall

 

Wall

Firestop (Round

 

Firestop

Termination Only)

 

Manual background Horizontal

Round

Termination

Round Termination

(Kit 01491 for V36, V42 Series Kit SDHTRK-58 CHDV Series)

Figure 14 - Horizontal Termination Configuration for Square or Round Terminations

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundForManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background.Manual backgroundManual backgroundManual backgroundManual background.comManual backgroundManual backgroundManual backgroundManual backgroundManual background

108861

Page 10
Image 10
Desa CHDV47NR, (V)V36N, CHDV47PR Horizontal Termination Configurations, Venting Installation Instructions, Continued