VENTING INSTALLATION INSTRUCTIONS

Installation for Vertical Termination

13

VENTING INSTALLATION INSTRUCTIONS

Continued

INSTALLATION FOR VERTICAL TERMINATION

Note: Vertical restrictor must be installed in all vertical installations.

1.Determine the route your vertical venting will take. If ceiling joists, roof rafters or other framing will obstruct the venting system, consider an offset (see Figure 19) to avoid cutting load bearing members. Note: Pay special attention to these installation instructions for required clearances (air space) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not pack air spaces with insu- lation. Also note maximum vertical rise of the venting system and any maximum horizontal offset limitations.

2.Set the fireplace in desired location. Drop a plumb line down from the ceiling to the position of the fireplace exit flue. Mark the center point where the vent will penetrate the ceiling. Drill a small locating hole at this point.

Drop a plumb line from the inside of the roof to the locating hole in the ceiling. Mark the center point where the vent will penetrate the roof. Drill a small locating hole at this point.

Roof Flashing

Wall Strap

45° Elbow

Ceiling Firestop

Figure 19 - Offset with Wall Strap and 45° Elbows

Flat Ceiling Installation

1.Cut a 10 3/4" square hole in the ceiling using the locating hole as a center point. The opening should be framed to 10 3/4"x10 3/4" (273 mm x 273 mm) inside dimensions, as shown in Figure 9 on page 8 using framing lumber the same size as the ceiling joists. If the area above the ceiling is an insulated ceiling or a room, nail firestop from the top side. This prevents loose insulation from falling into the required clearance space. Otherwise, install firestop below the framed hole. The firestop should be installed with no less than three nails per side (see Figure 20).

2.Assemble the desired lengths of pipe and elbows necessary to reach from the fireplace flue up through the firestop. Be sure all pipe and elbow connections are fully twist-locked (see Figure 8, page 8).

3.Cut a hole in the roof using the locating hole as a center point. (Cover any exposed open vent pipes before cutting hole in roof.) The 10 3/4"x10 3/4" hole must be measured on the horizontal; actual length may be larger depending on the pitch of the roof. There must be a 1" clearance from the vent pipe to combustible materials. Frame the opening as shown in Figure 9, page 8.

4.Connect a section of pipe and extend up through the hole.

Note: If an offset is needed to avoid obstructions, you must support the vent pipe every 3 feet. Use wall straps for this purpose (see Figure 19). Whenever possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less restriction to the flow of the flue gases and intake air.

5.Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flashing to the roof and framing with roofing nails. Be sure roofing material overlaps the top edge of the flashing as shown in Figure 19. There must be a 1" clearance from the vent pipe to combustible materials.

6.Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements described in Figure 7 on page 6. Note: You must increase vent height for steep roof pitches. Nearby trees, adjoining rooflines, steep pitched roofs and other similar factors may cause poor draft or down-drafting in high winds. Increasing the vent height may solve this problem.

7.Twist-lock the vent cap onto the last section of vent pipe.

Note: If the vent pipe passes through any occupied areas above the first floor, including storage spaces and closets, you must enclose pipe. You may frame and sheetrock the enclosure with standard construction material. Make sure and meet the minimum allow- able clearances to combustibles. Do not fill any of the required air spaces with insulation.

If area above is a room or

If area above is not a room, install

insulated area, install firestop

firestop below framed hole.

above framed hole.

 

Figure 20 - Installing Firestop

116235-01C

www.desatech.com

Page 13
Image 13
Desa (V)VC36PE, (V)VC36NE Installation for Vertical Termination, Flat Ceiling Installation, If area above is a room or

(V)VC36NE, (V)VC36PE specifications

Desa (V)VC36NE and (V)VC36PE are advanced probe technology designed for precise diagnostic and measurement applications in various industries, including manufacturing, automotive, and healthcare. These models are representative of Desa's commitment to innovation and excellence in engineering, providing users with essential features and cutting-edge technologies.

One of the main features of the (V)VC36NE model is its enhanced resolution, allowing for accurate data collection even in the most challenging environments. This high-resolution capability makes it ideal for detailed inspections and quality control, ensuring that manufacturers can meet stringent performance standards. Meanwhile, the (V)VC36PE model is equipped with a user-friendly interface that simplifies data interpretation, making it accessible to operators with varying levels of technical expertise.

Both models utilize advanced sensing technologies, including capacitive and resistive sensing, enabling them to capture real-time data with exceptional precision. This technology effectively reduces the margin for error, which is critical in applications where even minor discrepancies can lead to significant consequences. Furthermore, the integration of wireless communication in these models allows for seamless data transmission, enhancing connectivity and facilitating remote monitoring capabilities.

Another characteristic that sets Desa's (V)VC36NE and (V)VC36PE apart is their durability. Constructed with high-grade materials, they are designed to withstand harsh operating conditions, ensuring longevity and reliability. This robustness means that users can depend on these probes for consistent performance over time, reducing downtime and maintenance costs.

The versatility of the (V)VC36NE and (V)VC36PE models is another notable advantage. They are compatible with a broad range of accessories and can be easily integrated into existing systems, making them suitable for various applications across different sectors. Whether for industrial automation or healthcare diagnostics, these models provide excellent adaptability.

In conclusion, Desa’s (V)VC36NE and (V)VC36PE probes exemplify the brand's focus on delivering high-performance, reliable, and user-centric diagnostic solutions. Their advanced features, including high resolution, durable construction, and versatile compatibility, make them invaluable tools in modern industries, enhancing productivity and efficiency while ensuring high-quality outcomes.