FIREPLACE INSTALLATION

20

Checking Gas Connections (Cont.)

 

 

Removing/Replacing Glass Door

 

 

FIREPLACE INSTALLATION

Continued

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Figure 33).

2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fireplace or using compressed air.

3.Check all joints from propane/LP supply tank or gas meter to equip- ment shutoff valve (see Figure 34 for propane/LP or Figure 35 for natural gas). Apply noncorrosive leak detection fluid to all joints.

Bubbles forming show a leak. Correct all leaks at once.

Equipment

Open

Shutoff

 

 

Valve

 

 

 

 

Closed

Figure 33 - Equipment Shutoff Valve

 

 

Equipment

 

Propane/LP

Shutoff

 

Valve

 

Supply Tank

 

 

 

 

Gas Valve

 

Figure 34 - Checking Gas Joints for Propane/LP Gas Fireplace

Pressure Testing Fireplace Gas Connections

1.Open equipment shutoff valve (see Figure 33).

2.Open propane/LP supply tank valve for propane/LP fireplace or main gas valve located on or near gas meter for natural gas fireplace.

3.Make sure control knob of fireplace is in the OFF position.

4.Check all joints from equipment shutoff valve to gas valve (see Figure 34 for propane/LP or Figure 35 for natural gas). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

5.Light fireplace (see Operating Fireplace, page 23). Check all other internal joints for leaks.

6.Turn off fireplace (see To Turn Off Gas to Appliance, page 24).

REMOVING/REPLACING GLASS DOOR

CAUTION: Do not operate this fireplace with a broken glass door panel or without the glass door panel securely in place. For replacement part infor- mation see Replacement Parts, page 28.

CAUTION: Wear gloves and safety glasses while handling or removing broken glass. Do not remove if glass is hot. Keep children and pets away from glass.

WARNING: If fireplace has been running, turn off and unplug fireplace. Let cool before removing glass door or louvers.

Removing Louver Panels

Remove the top and bottom louver panels by simultaneously pulling both top end spring latches towards the center of the appliance until they are disengaged from the locating holes (see Figure 36). Repeat for bottom spring latches and pull the louvers outward. To install or replace items removed, simply reverse the procedures above.

Equipment

Shutoff

Valve

Gas

Meter

Gas Valve Figure 35 - Checking Gas Joints for Natural Gas Fireplace

Spring Latch

Louver Panel

Figure 36 - Removing Louver Panel

www.desatech.com

116237-01D

Page 20
Image 20
Desa (V)VC42NE Series, (V)VC42PE Series REMOVING/REPLACING Glass Door, Pressure Testing Fireplace Gas Connections

(V)VC42NE Series, (V)VC42PE Series specifications

The Desa (V)VC42NE Series and (V)VC42PE Series are advanced heating systems designed for residential and commercial applications. These models offer a unique combination of efficiency, performance, and user-friendly features, catering to diverse heating needs.

One of the standout features of both series is their exceptional energy efficiency. Utilizing cutting-edge technology, these heating solutions provide substantial savings on energy costs while minimizing environmental impact. The (V)VC42NE Series is particularly known for its low emissions, adhering to strict environmental regulations and contributing to cleaner air quality.

In terms of technology, the series incorporates innovative heating design and advanced materials. The high-efficiency burners ensure maximum heat output with minimal fuel consumption. Furthermore, the built-in diagnostics make it easy for homeowners and technicians to monitor performance and troubleshoot any issues that may arise, ensuring consistent and reliable operation over time.

The (V)VC42NE and (V)VC42PE models are equipped with user-friendly control systems. The intuitive interface allows users to set and adjust temperatures with ease, making it accessible for everyone. Additionally, these systems support programmable settings, enabling users to customize their heating schedules based on their lifestyle and preferences, thereby enhancing comfort and convenience.

Another essential characteristic of these series is their versatility in installation. With options for both vented and unvented configurations, users can choose the system that best fits their space and requirements. This flexibility allows for seamless integration into various environments, whether in homes, offices, or commercial establishments.

Safety is also a paramount focus in the design of the (V)VC42NE and (V)VC42PE Series. Built-in safety features, including flame failure devices and overheat protection, offer peace of mind to users by minimizing the risk of accidents.

Lastly, the sleek and modern appearance of these heating solutions ensures that they complement any décor. Their durable construction guarantees longevity, making the Desa series a reliable investment for those seeking effective heating solutions. In summary, the Desa (V)VC42NE Series and (V)VC42PE Series provide a potent combination of efficiency, safety, and user-friendly features, making them ideal choices for anyone in need of a dependable heating system.