Desa (V)VC42P SERIES Vertical Termination Configurations, Venting Installation Instructions

Models: (V)VC42P SERIES (V)VC42N SERIES

1 40
Download 40 pages 42.29 Kb
Page 14
Image 14
Vertical Termination Configurations

14

VENTING INSTALLATION INSTRUCTIONS

Installation for Vertical Termination (Cont.)

VENTING INSTALLATION INSTRUCTIONS

Continued

Vertical Termination Configurations

Figures 21 through 24 show four different configurations for verti- cal termination.

Venting with Two 90° Elbows

Vertical (V)

Horizontal (H1) +

 

Horizontal (H2)

5' min.

2' max.

6' min.

4' max.

7' min.

6' max.

8' min.

8' max.

20' max.

8' max.

45° Elbow

Note: Install

restrictor into inner

 

collar of fireplace

 

as shown.

Venting with One 90° Elbow

Vertical (V)

Horizontal (H)

5' min.

2' max.

6' min.

4' max.

7' min.

6' max.

8' min.

8' max.

20' max.

8' max.

45° Elbow

Note: Install

restrictor into inner

 

 

collar of fireplace

 

as shown.

Figure 22 - Vertical Venting Configuration Using One 90° Elbow (Vertical Round High Wind Termination Shown)

Figure 21 - Vertical Venting Configuration Using Two 90° Elbows with Two Horizontal Runs (Vertical Round High Wind Termination Shown)

Venting with Two 90° Elbows

Vertical (V1)

Horizontal (H)

5' min.

6' max.

6' min.

12' max.

7' min.

18' max.

8' min.

20' max.

Note: Install restrictor into inner collar of Venting with One 90° Elbow fireplace as shown.

45° Elbow

Note: Vertical (V1) + Vertical (V2) = 40' max.

Figure 23 - Vertical Venting Configuration Using Two 90° Elbows (Vertical Round High Wind Termination Shown)