Dometic 3308120.XXX Installation Instructions, Precautions, Choosing Location For The Unit

Models: 3308120.XXX

1 8
Download 8 pages 45.25 Kb
Page 4
Image 4
INSTALLATION INSTRUCTIONS

3308120.XXX GENESIS AIR FILTRATION SYSTEM

INSTALLATION INSTRUCTIONS

1.PRECAUTIONS

!WARNING

Improper installation may damage equip- ment/could endanger life, cause serious in- jury and/or property damage.

A.Read Installation and Operating Instructions carefully before attempting to start your air conditioner installa- tion.

B.Dometic Corporation will not be liable for any damages or injury incurred due to failure in following these instruc- tions.

C.Installation must comply with the National Electrical Code and any State or Local Codes or regulations.

D.DO NOT add any devices or accessories to this air conditioner except those specifically authorized by Dometic.

E.This equipment must be serviced by qualified personnel and some states require these people to be licensed.

2. CHOOSING LOCATION FOR THE UNIT

This air conditioner/heat pump is specifically designed for installation on the roof of a recreational vehicle (RV).

A.FOR ONE UNIT INSTALLATION:

The air conditioner/heat pump should be mounted slightly forward of center (front to back) and centered from side to side.

B.FOR TWO UNIT INSTALLATIONS:

Install one air conditioner/heat pump one-third and one air conditioner two-thirds from front of RV and centered from side to side. It is preferred that the air conditioner/ heat pump be installed in a relatively flat and level roof section measured with the RV parked on a level surface.

C.AFTER LOCATION HAS BEEN SELECTED:

1.Check for obstructions in the area where air condi- tioner/heat pump and return air cover will be in- stalled.

2.The roof must be designed to support 130 pounds when the RV is in motion. Normally a 200 lbs. static load design will meet this requirement.

CAUTION

It is the responsibility of the installer of this air conditioner/heat pump system to ensure structural integrity of the RV roof. Never cre- ate a low spot on the roof where water will collect. Water standing around the air con- ditioner/heat pump may leak into the inte- rior causing damage to the product and the RV.

3. AIR DISTRIBUTION SYSTEM SIZING &

DESIGN

The Installer of this air conditioner/heat pump system must design the air distribution system for his particular applica- tion. Several requirements for this system MUST be met for the air conditioner/heat pump to operate properly. These requirements are as follows:

A.Roof cavity thickness must be between 2.00" to 5.50". This distance is measured between roof and ceiling surface.

B.The total cross-sectional discharge area of outlet ducts from the plenum area under the air conditioner/heat pump must be a minimum of 16.0 sq. inches each side.

REGISTERS

8 MIN. — 12 MAX.

14 SQ. IN. FREE AREA PER REGISTER

REGISTER

TOTAL OUTLET

AIR AREA 16.0

REQUIRED

SQ. IN. MINIMUM

 

 

EACH SIDE

FIG. 1

DUCTS

MIN.

MAX.

DEPTH

2.00”

2-1/2"

WIDTH

8.00"

10.00"

TOTAL LENGTH

15'

40'

 

 

 

REGISTER

REQUIRED

14-1/4" (±1/8")

ROOF OPENING

REGISTER

REQUIRED

ROOF RAFTERS

4

Page 4