Blower Performance - Belt Drive
| Motor | Blower | Motor | Motor | Blower | Belt | Temp. | CFM @ .20 | |
| ext. static | ||||||||
Model | Size | Pulley | Pulley | Pulley | Size | Rise | |||
Size | pressure - in. | ||||||||
| (hp) | (in.) | Adjustment | (in.) | (in.) | (oF) | |||
|
| W.C. | |||||||
|
|
|
|
|
|
|
| ||
RLBF80C57B08 | 1/6 | 10 x 8 | 3 1/4 | 1 Turn | 7 | 40 | 45 - 75 | 980 | |
RLBF80C84/95B10 | 1/4 | 10 x 8 | 4 | Closed | 7 | 41 | 45 - 751 | 1300 | |
55 - 852 | |||||||||
|
|
|
|
|
|
|
| ||
RLBF80C112/125B16 | 3/4 | 12 x 9 | 4 | Closed | 7 | 42 | 50 - 801 | 1750 | |
55 - 852 | |||||||||
|
|
|
|
|
|
|
| ||
RLBR80C57B08 | 1/6 | 10 x 8 | 3 1/4 | 1 Turn | 7 | 40 | 50 - 80 | 860 | |
RLBR80C84/95B10 | 1/4 | 10 x 8 | 4 | Closed | 7 | 41 | 50 - 801 | 1220 | |
55 - 852 | |||||||||
|
|
|
|
|
|
|
| ||
RLBR80C112/125B16 | 3/4 | 12 x 9 | 4 | Closed | 7 | 42 | 55 - 851 | 1700 | |
60 - 902 | |||||||||
|
|
|
|
|
|
|
| ||
RLBR80C196B24 | 3/4 | 12 x 12 | 6 | Closed | 3 1/2 | 42 | 65 - 95 | 2660 |
1Low Fire Nozzle
2High Fire Nozzle
Alternate Motors for Cooling Combinations - Belt Drive
| Nominal | Motor | Blower | Motor | Motor | Blower | Belt | CFM @ | ext. static pressure - in. | ||||
Model | Cooling | Size | Size | Pulley | Pulley | Pulley | Size |
|
| W.C. |
|
| |
| Capacity | (in.) | (in.) | (in.) | Adjustment | (in.) | (in.) | .20 |
| .30 |
| .40 | .50 |
RLBF80C57B08 | 2.0 - 2.5 | 1/4 | 10 x 8 | 7 | Closed | 4 | 41 | 1,340* |
| 1,320* |
| 1,180 | 1,080 |
RLBF80C84/95B10 | 2.0 - 3.5 | 1/2 | 10 x 8 | 6 | Closed | 4 | 40 | 1,770 |
| 1,680 |
| 1,560 | 1,430 |
RLBF80C112/125B16 | 4.0 - 5.0 | 3/4 | 12 x 9 | 5 | Closed | 3 1/4 | 38 | 2,050 |
| 2,000 |
| 1,930 | 1,880 |
RLBR80C57B08 | 2.0 - 2.5 | 1/4 | 10 x 8 | 7 | Closed | 4 | 41 | 1,260 |
| 1,185 |
| 1,095 | 1,000 |
RLBR80C84/95B10 | 2.0 - 3.5 | 1/2 | 10 x 8 | 6 | Closed | 4 | 40 | 1,600 |
| 1,540 |
| 1,480 | 1,400 |
RLBR80C112/125B16 | 4.0 - 5.0 | 3/4 | 12 x 9 | 5 | Closed | 3 1/4 | 38 | 2,020 |
| 1,980 |
| 1,910 | 1,860 |
RLBR80C196B24 | 5.0 - 6.0 | 3/4 | 12 x 12 | 6 | Closed | 3 1/2 | 42 | 2,660 |
| 2,575 |
| 2,450 | 2,350 |
*Not recommended for heating. Temperature rise may be outside acceptable range. Note: Field converted with different size motor for cooling applications.