WIRING DIAGRAM
Wiring Requirements
•The bonding wire at least No. 8 AWG copper wire.
•Pull Copper current carrying conductors (one each: black, red, white, green), Use either No. 6 AWG 60º C, 8 AWG 75º C, or No. 8 AWG 90º C wire, if spa is 50 feet or less away from its power supply. Note: the ground must be equal to or larger than the largest power conductor.
Factory Recommended G.F.C.I. Load Center Wiring
Note: The white neutral wire from the back of the GFCI MUST be connected to an incoming line neutral. The internal mechanism of the GFCI requires this neutral connection. The GFCI will not work without it.
%DU1HXWUDO |
KLWH3LJWDLO
KLWH)URP6SD
1HXWUDO%DU
KLWH3LJWDLO |
7HITE 7IREE4OOTHET3PA
3PAP#ONTROL "OX
, . , '
./4% 7IRINGRORDERGMAYOVARY
BY MODEL #HECK THE LABEL ONETHE PACK ACCESSACOVEREFORSSPECIFIC
INSTRUCTIONS | |
|
CAUTION!
Note: Connection order may vary by pack model, please refer to equipment pack panel for proper connection order.