Eclipse Combustion 6500 instruction manual Troubleshooting Problem Possible Cause Solution

Models: 6500

1 46
Download 46 pages 30.86 Kb
Page 34
Image 34

TROUBLESHOOTING

 

 

 

PROBLEM

POSSIBLE CAUSE

SOLUTION

 

 

 

 

 

Cannot initiate start sequence

• Main valve is not closed.

Check proof-of-valve-closure switch.

 

 

 

 

 

 

 

• Air pressure switch has not made

Check air pressure switch adjustment.

 

 

contact.

Check air filter.

 

 

 

 

 

 

Check blower rotation.

 

 

 

Check outlet pressure from blower.

 

 

 

 

 

 

 

• High gas pressure switch has tripped.

Check incoming gas pressure; adjust

 

 

 

gas pressure if necessary.

 

 

 

Check pressure switch setting and

 

 

 

operation.

 

 

 

 

 

 

 

• Low gas pressure switch has tripped.

Check incoming gas pressure; adjust

 

 

 

gas pressure if necessary.

 

 

 

Check pressure switch setting and

 

 

 

operation.

 

 

 

 

 

 

 

• Malfunction of flame safeguard system

Have qualified electrician investigate

 

 

such as a shorted-out flame sensor

and rectify.

 

 

or electrical noise in the sensor line.

 

 

 

 

 

 

 

 

 

• Purge cycle not completed.

Check flame safeguard system, or

 

 

 

purge timer.

 

 

 

 

 

 

 

• Main power is off.

Make sure power is on to control

 

 

 

system.

 

 

 

 

 

 

 

• No power to control unit.

Call qualified electrician to

 

 

 

investigate.

 

 

 

 

 

Scrambled messages on remote

• Improper grounding in system.

Check grounding in system.

display.

 

 

 

 

 

 

 

 

“UNSAFE AIR SHORT” message

• Improperly adjusted air switch.

Check air switch settings.

appears on display.

• Air switch either shorted or wired

Check wiring to air switch.

 

 

 

 

wrong.

 

 

 

 

 

 

 

Burner flame fails but no flame

• A faulty scanner.

Check scanner as explained in

failure indication occurs.

 

checklists in “Maintenance” portion

 

 

 

of this Section.

 

 

 

 

 

 

 

• Improperly connected sensor wires.

Check wiring diagram on page 26

 

 

 

as well as appropriate sensor

 

 

 

information in Section 7.

 

 

 

 

 

 

 

• Electrical interference from other

Check Note information on page

 

 

current carrying wires.

27 regarding sensor wiring.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

34

Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03

 

Page 34
Image 34
Eclipse Combustion 6500 Troubleshooting Problem Possible Cause Solution, Contact Check air filter Check blower rotation