![](/images/new-backgrounds/1010132/1013267x1.webp)
TROUBLESHOOTING |
|
|
| |
PROBLEM | POSSIBLE CAUSE | SOLUTION | ||
|
|
|
|
|
Cannot initiate start sequence | • Main valve is not closed. | Check | ||
|
|
|
|
|
|
| • Air pressure switch has not made | Check air pressure switch adjustment. | |
|
| contact. | Check air filter. | |
|
|
| ||
|
|
| Check blower rotation. | |
|
|
| Check outlet pressure from blower. | |
|
|
|
|
|
|
| • High gas pressure switch has tripped. | Check incoming gas pressure; adjust | |
|
|
| gas pressure if necessary. | |
|
|
| Check pressure switch setting and | |
|
|
| operation. | |
|
|
|
|
|
|
| • Low gas pressure switch has tripped. | Check incoming gas pressure; adjust | |
|
|
| gas pressure if necessary. | |
|
|
| Check pressure switch setting and | |
|
|
| operation. | |
|
|
|
|
|
|
| • Malfunction of flame safeguard system | Have qualified electrician investigate | |
|
| such as a | and rectify. | |
|
| or electrical noise in the sensor line. |
|
|
|
|
|
|
|
|
| • Purge cycle not completed. | Check flame safeguard system, or | |
|
|
| purge timer. | |
|
|
|
|
|
|
| • Main power is off. | Make sure power is on to control | |
|
|
| system. | |
|
|
|
|
|
|
| • No power to control unit. | Call qualified electrician to | |
|
|
| investigate. | |
|
|
|
|
|
Scrambled messages on remote | • Improper grounding in system. | Check grounding in system. | ||
display. |
|
|
| |
|
|
|
|
|
“UNSAFE AIR SHORT” message | • Improperly adjusted air switch. | Check air switch settings. | ||
appears on display. | • Air switch either shorted or wired | Check wiring to air switch. | ||
|
| |||
|
| wrong. |
|
|
|
|
|
|
|
Burner flame fails but no flame | • A faulty scanner. | Check scanner as explained in | ||
failure indication occurs. |
| checklists in “Maintenance” portion | ||
|
|
| of this Section. | |
|
|
|
|
|
|
| • Improperly connected sensor wires. | Check wiring diagram on page 26 | |
|
|
| as well as appropriate sensor | |
|
|
| information in Section 7. | |
|
|
|
|
|
|
| • Electrical interference from other | Check Note information on page | |
|
| current carrying wires. | 27 regarding sensor wiring. | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|