Eclipse Combustion CAH, TAH, DAH manual Mounting& Duct Lengths, In-Duct, Sealed, Slot-Fired

Models: CAH DAH AH TAH

1 8
Download 8 pages 39.48 Kb
Page 5
Image 5
Figure 5–Mounting & Duct Lengths

Figure 5–Mounting & Duct Lengths

In-Duct

Min./Max. Velocity: 500 to 6000 fpm 2.54 to 30.48 m/s

Optimum Velocity: 1000 to 4000 fpm 5.08 to 20.32 m/s

Provide at least 3" (76 mm) clear- ance between burner and top, bot- tom and sides of the duct.

Profile plates are not required for good burner operation, but uni- form velocity must be maintained for full length of burner. If velocity is not uniform, profile plates can be used to correct this condition.

Sealed

Duct Press: +0.2" to –0.5" w.c. +0.5 to –1.2 mbar

Min./Max. Velocity: 500 to 1200 fpm

2.54 to 6.10 m/s

Min./Max. Velocity: 500 to 1200 fpm

2.54 to 6.10 m/s

Slot-Fired

Duct Press: 0" to –0.5" w.c. 0 to –1.2 mbar

Min./Max. Velocity: 500 to 1200 fpm

2.54 to 6.10 m/s

Min./Max. Velocity: 500 to 1200 fpm

2.54 to 6.10 m/s

Guidelines for All Mounting Arrangements

Center the burner in the duct.

Allow a minimum of 46" (1168 mm) from burner to nearest point of possible flame impingement at an input of 1,000,000 Btu/hr. (962 kW/m).

On burners longer than 36" (914 mm), use a hanger or a pedes- tal to support the blower and motor.

Min./Max. Velocity: 500 to 6000 fpm 2.54 to 30.48 m/s

Optimum Velocity: 1000 to 4000 fpm 5.08 to 20.32 m/s

Duct Lengths

Minimum Distance Before Transition

Rectangular Ducts: One Height or Width, Whichever is Greater

Round Ducts: One Diameter

7.5°

Maximum

Air Flow

AH

Burner

Minimum Distance Before

In-DuctSealed Possible Flame Impingement = 46"

Eclipse AirHeat v1.0 - Installation Guide No. 140, 11/4/03

5

Page 5
Image 5
Eclipse Combustion CAH Mounting& Duct Lengths, In-Duct, Sealed, Slot-Fired, Duct Press +0.2 to -0.5w.c. +0.5 to -1.2mbar