alarm cancel signal within that period. It switches the relay for 5 seconds with the switch in pulse mode.

Low Battery Indication: Red light flashes every 10 seconds. (The green light switches off when the red is on).

Size of System: : the recommended maximum number of Radiolink units should not exceed 12 i.e any combination of relays, smoke alarms and remote controls to a maximum of 12 in total. Contact the Technical Services Department at one of the addresses below for advice on systems requiring more than this.

Communication: All units will communicate with other uncoded devices (e.g. Smoke Alarms) as shipped. After a unit has been house coded it will only communicate with other units house coded at the same time. House coding is essen- tial to prevent false alarms from neighbouring systems.

Entering House Code Mode: Pressing and holding the House Code switch until the red light comes on puts the RadioLink Relay into House code mode.

House Code Mode: The RadioLink Relay transmits and receives specific Codes. The red light flashes once every 5 seconds (interupting the green light) for each unit’s code it memorises (including itself). Only 12 flashes can be counted in house code mode – so communication among more than 12 devices has to be done functionally with the test buttons etc.

Duration of House Code Mode: 15 minutes

Clearing House Codes: The house codes memorised can be deleted (i.e. the RadioLink Relay can be uncoded) by press- ing and holding the House Code switch on for about 6 sec- onds. The red light will come on and then flash slowly to Indicate the smoke alarm has been returned to the default Factory settings.

Aico Ltd.,

Mile End Business Park,

Maesbury Road, Oswestry,

Shropshire SY10 8NN, U.K.

Telephone: 0870 7584000

www.aico.co.uk

Ei Electronics,

Shannon Industrial Estate,

Shannon, Co. Clare, Ireland.

Telephone: +353 61 471277

www.eielectronics.com

© Ei Electronics 2004

P/N A15267 Rev 0