SPECIFICATIONS
Load Output Relay: |
| Ratings (Maximum): | ||
|
| 120VAC 208VAC 240VAC | ||
Full Load Amps NC & Load | 16 A | 9.2 A | 8 A | |
Locked Rotor Amps NC & Load | 96 A | 55.2 A | 48 A | |
16 A | 16 A | 16 A | ||
Horsepower NC & Load |
| 1 hp | 1 hp | 1 hp |
24 VAC NC & Load | 100 VA, 30 VAC Max (Class 2) | |||
Pilot Duty NC & Load | 125 VA, 24 to 240 VAC |
|
•Minimum Load Rating: 1 Amp @ 24 VAC
•Note: the above minimum current/voltage is specified to assure proper operation.
NOTE: For use on single phase circuits only.
Alarm Relay Ratings (Maximum):
N.O. contact: 1 Amp, 5 to 24 V, AC or DC
Temperature Probes:
NTC
The control is shipped with an NTC (Negative Temperature Coefficient) sensor, with a cable length of 7½ feet. Cable length can be extended up to 400 feet by appropriately splic- ing and adding additional cable (22 AWG or larger diameter)
Operating Ambient Ratings (Control Enclosure):
Operating Temperature: | |
Storage Shipping Ambient Ratings: | |
Storage Temperature: | |
Operating Humidity: | 0 to 95% Relative Humidity, |
| |
Maximum Dew Point: | 85°F (29°C) |
Temperature
Differential Range: | 1 to 30 (Degrees F or Degrees C) |
Case:
NEMA 1 Enclosure, Flammability Rating: UL94VO
as needed – polarity is not important. When extending cable length, verify temperature accuracy and use the menu Ambi- ent Temperature Offset (OFS) settings to compensate accord- ingly if required.
|
|
| NTC TEMPERATURE VERSUS RESISTANCE TABLES |
|
| ||||||
|
|
|
|
|
|
|
|
| |||
Temperature | Resistance |
|
| Temperature | Resistance |
| Temperature | Resistance | |||
(°F) | (°C) | (KΩ) |
|
| (°F) | (°C) | (KΩ) |
| (°F) | (°C) | (KΩ) |
|
|
|
|
|
|
|
|
|
|
|
|
328.29 |
|
| 50 | 10 | 19.82 |
| 140 | 60 | 2.49 | ||
236.83 |
|
| 59 | 15 | 15.67 |
| 149 | 65 | 2.09 | ||
172.90 |
|
| 68 | 20 | 12.48 |
| 158 | 70 | 1.76 | ||
127.65 |
|
| 77 | 25 | 10.00 |
| 167 | 75 | 1.48 | ||
95.23 |
|
| 86 | 30 | 8.07 |
| 176 | 80 | 1.26 | ||
5 | 71.74 |
|
| 95 | 35 | 6.55 |
| 185 | 85 | 1.07 | |
14 | 54.56 |
|
| 104 | 40 | 5.34 |
| 194 | 90 | 0.92 | |
23 | 41.85 |
|
| 113 | 45 | 4.38 |
| 203 | 95 | 0.79 | |
32 | 0 | 32.37 |
|
| 122 | 50 | 3.61 |
| 212 | 100 | 0.68 |
41 | 5 | 25.23 |
|
| 131 | 55 | 2.99 |
| 221 | 105 | 0.59 |
PTC
The control may be connected to an existing PTC (Positive Temperature Coefficient) sensor. Make sure the PTC sensor meets the specifications tables below. Failure to do so will result in temperature inaccuracies. The PTC input may not be
extended more than 50 feet, and the wire gauge should be
18 AWG wire or larger diameter. Be sure the probe attached matches the resistance vs. temperature tables or temperature inaccuracies may occur.
|
|
| PTC TEMPERATURE VERSUS RESISTANCE TABLES |
|
| ||||||
|
|
|
|
|
|
|
|
| |||
Temperature | Resistance |
|
| Temperature | Resistance |
| Temperature | Resistance | |||
(°F) | (°C) | (KΩ) |
|
| (°F) | (°C) | (KΩ) |
| (°F) | (°C) | (KΩ) |
|
|
|
|
|
|
|
|
|
|
|
|
613 |
|
| 50 | 10 | 924 |
| 140 | 60 | 1323 | ||
640 |
|
| 59 | 15 | 960 |
| 149 | 65 | 1368 | ||
668 |
|
| 68 | 20 | 997 |
| 158 | 70 | 1413 | ||
697 |
|
| 77 | 25 | 1035 |
| 167 | 75 | 1459 | ||
727 |
|
| 86 | 30 | 1074 |
| 176 | 80 | 1506 | ||
5 | 758 |
|
| 95 | 35 | 1113 |
| 185 | 85 | 1554 | |
14 | 789 |
|
| 104 | 40 | 1153 |
| 194 | 90 | 1602 | |
23 | 822 |
|
| 113 | 45 | 1194 |
| 203 | 95 | 1652 | |
32 | 0 | 855 |
|
| 122 | 50 | 1236 |
| 212 | 100 | 1702 |
41 | 5 | 889 |
|
| 131 | 55 | 1279 |
| 221 | 105 | 1753 |
7