CONTROLLER (continued) | Series 185 |
|
|
6 --- Remote Control Features
These remote control features require a customer– supplied
Remote test
Table E. Remote test
Function | Factory | DIP | DIP | Actuator | |
Setting | Switch | Actuator | Position | ||
| |||||
|
|
|
|
| |
disabled | disabled | S3 | 3 | on (up) | |
enabled | (on) | off (down) | |||
|
|
Remote test (with automatic retransfer)
Table F. Remote transfer to generator
Function | Factory | DIP | DIP | Actuator | |
Setting | Switch | Actuator | Position | ||
| |||||
|
|
|
|
| |
disabled | disabled | S3 | 2 | on (up) | |
enabled | (on) | off (down) | |||
|
|
Bypass load transfer to utility time delay
Table G. Bypass load transfer to utility time
delay
Function | Factory | DIP | DIP | Actuator | |
Setting | Switch | Actuator | Position | ||
| |||||
|
|
|
|
| |
disabled | disabled | S3 | 1 | on (up) | |
enabled | (on) | off (down) | |||
|
|
7 --- Factory Settings --- Summary
Table H. Factory Settings – Summary
DIP Switch | DIP Actuator | Actuator Position | |
|
|
| |
| 1 | on (up) | |
|
|
| |
| 2 | off (down) | |
|
|
| |
| 3 | on (up) | |
|
|
| |
| 4 | off (down) | |
|
|
| |
S1 | 5 | off (down) | |
|
| ||
6 | on (up) | ||
| |||
|
|
| |
| 7 | off (down) | |
|
|
| |
| 8 | off (down) | |
|
|
| |
| 9 | off (down) | |
|
|
| |
| 10 | on (up) | |
|
|
| |
| 1 | off (down) | |
|
|
| |
| 2 | on (up) | |
|
|
| |
| 3 | off (down) | |
|
|
| |
| 4 | on (up) | |
|
|
| |
S2 | 5 | on (up) | |
|
| ||
6 | on (up) | ||
| |||
|
|
| |
| 7 | on (up) | |
|
|
| |
| 8 | on (up) | |
|
|
| |
| 9 | off (down) | |
|
|
| |
| 10 | off (down) | |
|
|
| |
| 1 | on (up) | |
|
|
| |
| 2 | on (up) | |
|
|
| |
| 3 | on (up) | |
|
|
| |
| 4 | on (up) | |
|
|
| |
S3 | 5 | on (up) | |
|
| ||
6 | off (down) | ||
| |||
|
|
| |
| 7 | on (up) | |
|
|
| |
| 8 | on (up) | |
|
|
| |
| 9 | on (up) | |
|
|
| |
| 10 | on (up) | |
|
|
|