6 --- Remote Control Features

CONTROLLER (continued)

Series 185

 

 

6 --- Remote Control Features

These remote control features require a customer– supplied normally–closed contact suitable for a 5 V dc low energy circuit. Refer to the wiring diagram provided with the ATS. Activate the appropriate DIP switch S3 actuators as shown in Tables E, F, or G. See Figure 7.

Remote test

Normally–closed input. When opened, it simulates a utility failure. The generator is signalled to start immediately and the load transfers to the generator (if acceptable). If the generator fails, the load stays on the generator until the remote test circuit is closed.

Table E. Remote test

Function

Factory

DIP

DIP

Actuator

Setting

Switch

Actuator

Position

 

 

 

 

 

 

disabled

disabled

S3

3

on (up)

enabled

(on)

off (down)

 

 

Remote test (with automatic retransfer)

Normally–closed input. When opened, it simulates a utility failure. The generator is signalled to start immediately and the load transfers to the generator (if acceptable). If the generator fails, the load transfers back to the utility (if acceptable).

Table F. Remote transfer to generator

Function

Factory

DIP

DIP

Actuator

Setting

Switch

Actuator

Position

 

 

 

 

 

 

disabled

disabled

S3

2

on (up)

enabled

(on)

off (down)

 

 

Bypass load transfer to utility time delay

Normally–closed input. When opened, it bypasses or cancels the generator to utility load transfer time delay. The load transfers back to the utility.

Table G. Bypass load transfer to utility time

delay

Function

Factory

DIP

DIP

Actuator

Setting

Switch

Actuator

Position

 

 

 

 

 

 

disabled

disabled

S3

1

on (up)

enabled

(on)

off (down)

 

 

7 --- Factory Settings --- Summary

Table H. Factory Settings – Summary

DIP Switch

DIP Actuator

Actuator Position

 

 

 

 

1

on (up)

 

 

 

 

2

off (down)

 

 

 

 

3

on (up)

 

 

 

 

4

off (down)

 

 

 

S1

5

off (down)

 

 

6

on (up)

 

 

 

 

 

7

off (down)

 

 

 

 

8

off (down)

 

 

 

 

9

off (down)

 

 

 

 

10

on (up)

 

 

 

 

1

off (down)

 

 

 

 

2

on (up)

 

 

 

 

3

off (down)

 

 

 

 

4

on (up)

 

 

 

S2

5

on (up)

 

 

6

on (up)

 

 

 

 

 

7

on (up)

 

 

 

 

8

on (up)

 

 

 

 

9

off (down)

 

 

 

 

10

off (down)

 

 

 

 

1

on (up)

 

 

 

 

2

on (up)

 

 

 

 

3

on (up)

 

 

 

 

4

on (up)

 

 

 

S3

5

on (up)

 

 

6

off (down)

 

 

 

 

 

7

on (up)

 

 

 

 

8

on (up)

 

 

 

 

9

on (up)

 

 

 

 

10

on (up)

 

 

 

5

381333–319 A

Page 7
Image 7
Emerson 185 Remote Control Features, Table E. Remote test, Remote test with automatic retransfer, CONTROLLER continued