Carbon Dioxide Sensor
Product Information Sheet |
Figure 3 - CO2 Sensor Reassembly
Setting the Volts/Amps Switch
The front of the circuit board has a switch that controls whether the analog output sends a signal as voltage (V) or milliamps (mA). To work with CPC I/ O boards, this switch should be set to voltage (the DOWN position). Verify this switch is in the DOWN position before operating the sensor.
Setting Up the CO2
Sensor Software
Before operating the sensor, you must use the LCD display and the three buttons on the front of the circuit board to set the sensor’s operating parameters. Figure 4 shows the keys on the circuit board and the setup screens. Use the ENTER key to cycle through the setup screens, and the + and - keys to adjust parameter values.
Figure 4 - CO2 Sensor Keys and Screens
Setpoint
If you are using the CO2 sensor’s relay for alarming or control, use the + and - keys to adjust the value of the set point. When the CO2 sensor’s reading is above this set point, the relay will energize. Press ENTER to save the setpoint value.
Altitude
To properly measure CO2 concentrations, you must specify the approximate altitude of the site. Use the + and - keys to select the number of feet above sea level closest to the site’s altitude. Press ENTER to save the altitude value.
CO2 Calibration
WARNING! Calibrating the CO2 sensor requires a gas calibration kit. DO NOT perform a calibration without this kit, or else the sensor will give erroneous readings.
All CO2 sensors are shipped