INSTALLATION
Engine Starting Contacts
Customer connections for engine control contact and TS auxiliary contacts connections are located on terminal block TB which is mounted on the front lower left of the transfer switch. Refer to wiring diagram provided with the Series 300 ATS and connect the engine start wires to the appropriate terminals.
See Figure
(continued)
left side of
transfer switch
Table A. Engine start
connections.
When normal | Terminals | |
on transfer | ||
source fails | ||
switch | ||
| ||
contact closes | TB1 and TB2 | |
contact opens | TB1 and TB3 |
Auxiliary Circuits
Connect auxiliary circuit wires to appropriate terminals on transfer switch terminal block TB as shown on the wiring diagram provided with this Automatic Transfer Switch. Make the necessary auxiliary connections by referring
COMMON
FEATURE 7
closes to start
FEATURE 8
opens to start
COMMON
FEATURE 14B
closed on emergency
FEATURE 14A
closed on normal
COMMON
FEATURE 14BA
closed on emergency
FEATURE 14AA
closed on normal
Engine Starting
Signals
5 amps, 32 V DC
5 amps resistive 28 V DC
or 120 V AC max.
TS Auxiliary Contacts Feature 14A & 14B
10 amps, 32 V DC
10 amps 250 V AC
general purpose
Optional
TS Auxiliary Contacts
Feature 14AA & 14BA
10 amps, 32 V DC
10 amps 250 V AC
general purpose
terminal block for engine start and
auxiliary circuit connections
Connections to Controller
for other Control FeaturesFigure
(located on bottom of Controller)
Load Disconnect | Programmable |
Feature | Engine Exerciser |
Connections | connection, |
(see Wiring Diagram | if provided |
& refer to page | (refer to |
for DIP switch settings) page
Remote Control Features Connections |
|
(refer to the Wiring Diagram & |
|
page |
|
Each control contact must be suitable | for factory |
for a 5 V DC low energy circuit. | use only |
Figure