European Certifications
I1 ATEX Intrinsic Safety
-HART/Remote Display/Quick Connect/HART Diagnostics
Certificate No.: BAS01ATEX1303X II 1 G
Ex ia IIC T4 (-60 °C Tamb 70 °C)
1180
Special Conditions for Safe Use (X)
1. The apparatus, excluding the Types 3051 S-T and 3051 S-C (In-line and Coplanar
SuperModule Platforms respectively), is not capable of withstanding the 500 V test as
defined in Clause 6.3.12 of EN 60079-11. This must be considered during installation.
2. The terminal pins of the Types 3051 S-T and 3051 S-C must be protected to IP20
minimum.
N1 ATEX Type n
Certificate No.: BAS01ATEX3304X II 3 G
Ex nL IIC T5 (-40 °C Tamb 70 °C)
Ui = 45 Vdc max
Ci = 11.4 nF
Li = 0
For remote display, Ci = 0, Li = 60 µH
IP66
Special Conditions for Safe Use (x)
The apparatus is not capable of withstanding the 500 V insulation test required by Clause
6.8.1 of EN 60079-15. This must be taken into account when installing the apparatus.
NOTE
RTD Assembly is not included with the 3051SFx Type n Approval.
Table 3. Input Parameters
Loop / Power Groups
Ui = 30 V All
Ii = 300 mA All
Pi = 1.0 W All
Ci = 30 nF SuperModule Platform
Ci = 11.4 nF HART / HART Diagnostics / Quick Connect
Ci = 0 Remote Display
Li = 0 All Except Remote Display
Li = 60 µH Remote Display
RTD Assembly (3051SFx Option T or R)
Ui = 5 Vdc
Ii = 500 mA
Pi = 0.63 W