Emerson 460 Installation of hold-downclips in pairs, Cable laid in straight patterns

Models: 460

1 16
Download 16 pages 37.22 Kb
Page 13
Image 13
Figure 5 Installation of hold-down clips in pairs

4.The installation of the hold-down clips should be in pairs according to Figure 5 with the following considerations:

Figure 5 Installation of hold-down clips in pairs

a. One pair every 6 to 8 feet in straight patterns (see Figure 6). b. One pair every 3 to 4 feet in circular patterns (see Figure 7).

c.One pair at the beginning and end of the arc when turning 90 degrees (see Figure 8).

d.One pair as needed to maintain consistent uniform contact between the floor and detection cable.

Figure 6 Cable laid in straight patterns

Hold-down clips every 6-8 ft.

Figure 7 Cable laid in circular patterns

Hold-down clips every Figure 6 Cable laid in straight patternsFigure 7 Cable laid in circular patterns 3-4 ft.

Figure 8 90° turn in cable

Hold-down clips at beginning & end of arc

5.Be certain the detection cable is protected from the adhesive instal- lation for the hold-down clips. No adhesive should come in contact with the detection cable.

6.Once adhesive is completely dry, snap the cable into each hold-down clip.

7.Check that there are no gaps between the floor and detection cable. (Add clips as required.)

8.Be certain there are no alarms present on the module.

9.Do final testing as per instruction in Step 2.