Placement on Subfloor Under Cooling Support Equipment

(Other applications such as long perimeter walls can be monitored)

To a Liebert environmental unit and an optional* monitoring panel

To external

 

 

power

 

Leak

supply or

 

detection

directly

 

cable

from

 

 

unit

 

Leak detection

(see

 

 

zone (directly

Power Wiring

 

 

beneath unit)

on page 3)

LT460

 

*Output connections to external alarm monitoring panels such as the Liebert contact closure alarm panels

As shown above, the Liqui-tect 460 (LT460) may be placed on a sub- floor, where it is connected to the leak detection cable that surrounds the leak detection zone—the area directly beneath the unit being protected or other areas such as the perimeter of a room.

Note: For a downflow unit, the leak detection cable must be located six feet in front of the unit.

The LT460 requires a 24 VAC power supply either from the environ- mental unit or an external source. There are two sets of Form-C dry contacts for connection to a Liebert environmental unit and an exter- nal monitoring panel.

For more information:

See Installation of Leak Detection System Cable on page 8 for instructions on installing the cable and proper placement of the hold-down clips.

See Leak Detection Kit Installation Scenarios on page 10 for cable placement, distance from the unit, and part numbers.