Placement on Subfloor Under Cooling Support Equipment
(Other applications such as long perimeter walls can be monitored)
To a Liebert environmental unit and an optional* monitoring panel
To external |
|
| |
power |
| Leak | |
supply or |
| detection | |
directly |
| cable | |
from |
|
| |
unit |
| Leak detection | |
(see |
| ||
| zone (directly | ||
Power Wiring |
| ||
| beneath unit) | ||
on page 3) | LT460 | ||
|
*Output connections to external alarm monitoring panels such as the Liebert contact closure alarm panels
As shown above, the
Note: For a downflow unit, the leak detection cable must be located six feet in front of the unit.
The LT460 requires a 24 VAC power supply either from the environ- mental unit or an external source. There are two sets of
For more information:
•See Installation of Leak Detection System Cable on page 8 for instructions on installing the cable and proper placement of the
•See Leak Detection Kit Installation Scenarios on page 10 for cable placement, distance from the unit, and part numbers.