Configuration Switch Settings
A | Switch Settings |
| OFF | ON | ||
select two alarm (filter) delays and |
| |||||
1. Leak Detect Filter |
| 10sec | 2min | |||
three mutually exclusive alarm | 2. Alarm Latch |
| S1 | No | Yes | |
modes. The switches are located | 3. Alarm Retest Delay | No | 1hr | |||
4. Not Used |
|
| — | — | ||
next to the wiring termination | ALL CIRCUITS: CLASS 2 |
| ||||
blocks. |
| |||||
Contacts shown in POWERED, | ||||||
Leak Detect Filter Delay(SS1) | Contacts |
| N.C. | 2 | ||
Rating: |
| C | ||||
SS1 selects the leak detect filter | 24V,3A |
| N.O. |
| ||
|
|
| ||||
delay, the interval for which a leak | Contacts |
| N.C. |
| ||
condition must be continuously | Rating: |
| C | 1 | ||
detected before an alarm is | 24V,3A |
| N.O. |
| ||
triggered: | 24V |
|
|
| ||
OFF = 10 seconds (default) | 50/60Hz |
|
|
| ||
0.12A |
|
|
| |||
ON = 2 minutes | CONNECT ENCLOSURE TO EARTH GROUND | |||||
This feature is useful for eliminat- | ||||||
|
|
|
|
| ||
ing nuisance alarms. SS1 works |
|
|
|
|
| |
independently of the settings of SS2 |
|
|
|
|
|
and SS3. While the alarm delay is selectable (factory default is OFF=10 seconds), the cable fault delay is preset at approximately 2 seconds.
Latching or Non-Latching Alarms (SS2)
SS2 selects latching or
OFF =
The factory default is