Emerson 460 installation manual Configuration Switch Settings, Leak Detect Filter DelaySS1

Models: 460

1 16
Download 16 pages 37.22 Kb
Page 9
Image 9
Configuration Switch Settings

Configuration Switch Settings

A four-position DIP switch is used to

Switch Settings

 

OFF

ON

select two alarm (filter) delays and

 

1. Leak Detect Filter

 

10sec

2min

three mutually exclusive alarm

2. Alarm Latch

 

S1

No

Yes

modes. The switches are located

3. Alarm Retest Delay

No

1hr

4. Not Used

 

 

next to the wiring termination

ALL CIRCUITS: CLASS 2

 

blocks.

 

Contacts shown in POWERED, NON-ALARM state

Leak Detect Filter Delay(SS1)

Contacts

TB3-3

 

N.C.

2

Rating:

TB3-2

 

C

SS1 selects the leak detect filter

24V,3A

TB3-1

 

N.O.

 

 

 

 

delay, the interval for which a leak

Contacts

TB2-3

 

N.C.

 

condition must be continuously

Rating:

TB2-2

 

C

1

detected before an alarm is

24V,3A

TB2-1

 

N.O.

 

triggered:

24V

TB1-2

 

 

 

OFF = 10 seconds (default)

50/60Hz

TB1-1

 

 

 

0.12A

 

 

 

ON = 2 minutes

CONNECT ENCLOSURE TO EARTH GROUND

This feature is useful for eliminat-

 

 

 

 

 

ing nuisance alarms. SS1 works

 

 

 

 

 

independently of the settings of SS2

 

 

 

 

 

and SS3. While the alarm delay is selectable (factory default is OFF=10 seconds), the cable fault delay is preset at approximately 2 seconds.

Latching or Non-Latching Alarms (SS2)

SS2 selects latching or non-latchingalarms, the setting in which an alarm will latch ON until manually reset:

OFF = Non-latching (default) ON = Latching

The factory default is OFF=Non-latching. If the sensor is in latching mode (ON=Latching) and the leak condition clears itself in the interim, a manual reset is required. While the alarm is latched, the sensor goes into a “sleep” mode and power to the leak detection cable is discontinued. De-powering the cable prevents damage to the cable should it be in contact with the conductive liquid for an extended duration. After a manual reset, the sensor resumes its normal opera- tion, continuously checking for leaks. If the leak condition has not yet cleared but the sensor is manually reset, the sensor will re-alarm after the appropriate leak detect filter delay. SS2 in the ON position will disable the operation of SS3.