INTEGRATED FURNACE

INTEGRATED FURNACE

 

TROUBLESHOOTING

CONTROL MODULE

 

GUIDE

 

 

 

 

 

 

 

 

 

 

!WARNING

Failure to read and follow all instructions carefully before in- stalling or operating this control, could cause personal injury and/ or property damage.

50A55 INTEGRATED FURNACE CONTROL MODULE

Qualified Serviceman’s Troubleshooting Guide

TROUBLESHOOTING PROCEDURE

If the light on the module is on continuously, the fault is likely to be internal to the module. To make sure, interrupt line or 24 volt thermostat power for a few seconds and then restore. If internal fault is indicated again, and flame sensor is not shorted to ground, replace control. A flashing light indicates the problem is most likely in the external components or wiring. Proceed as follows:

!WARNING

Turn power off before any troubleshooting or servicing begins.

Line voltage (120 VAC) could be present on the surface of the ignitor, if the sys- tem is not correctly wired. Such voltage can cause serious injury or death.

The following steps must be performed first before any troubleshooting begins.

1)Disconnect electric power to system at main fuse or circuit breaker.

2)Visually inspect equipment for apparent damage. Check wiring for loose connections.

3)Check for proper grounding and reversed polarity.

A.Check continuity for C terminal on module to electrical service ground and connection at the furnace junction box. If ground connection is open, check module ground connection and the electrical service ground connection.

Repair and retest.

B.Re-connect electric power to system.

C.Check for voltage between the line neutral terminal and furnace ground. If voltage exists, the main power supply lines are improperly connected to the furnace (REVERSED POLARITY). Again disconnect electric power to system; then reverse incoming supply leads to furnace. Repeat step.

D.Recheck system for proper operation.

If neither apparent damage, loose connection nor reversed polarity is the problem, proceed to troubleshooting chart or fault index chart that is suggested by the actual condition.

NOTE: This troubleshooting guide is not for 50A55-4XX modules found on Trane equipment or 50A55-1XX modules found on Lennox equipment.

FAULT INDEX CHART

No manual fan

1A

- 1K

Power supply and voltage

1C - 1G

No fan at cooling speed

2A

- 2L

No induced draft motor

3A

- 3H

LED flashing 2X without inducer

3E

 

LED flashing 3X with inducer

3I - 3O

Ignitor does not glow

4A

- 4D

Burner does not stay lit

4E - 4N

Gas supply problem

4F - 4K

No outlet pressure

4H - 4J

Gas valve does not energize

4L - 4N

Flame sensor fault

5A

- 5P

Burner ground

5K

 

Polarity check

5L - 5M

Ignitor stays on after burner ignition

5B - 5C