CHART 1

TROUBLESHOOTING

 

INTEGRATED FURNACE

GUIDE

 

CONTROL MODULE

 

 

 

 

 

 

 

 

 

 

CHART 1

Place

1A1B

Indoor Blower

Check

1C

Does LED

flash 1 time YES when disconnect

is turned

ON?

NO

thermostat

fan switch in

the ON

position.

1D

Is 24V

present at YES control

terminals

R & C?

NO

Replace control.

Check operation.

Does indoor

YES

blower run at

 

HEAT speed?

 

NO

1E

Is 24V

present at YES control

terminals

G & C?

NO

Return fan

switch to

AUTO position.

1F

Is 120V

 

Indoor blower

present at

YES

fault. Repair or

control terminals

 

replace. Check

COOL & CIR

 

 

operation.

NEUTRAL?

 

 

 

NO

 

 

 

 

Replace control.

 

 

Check operation.

 

 

Repair wiring

 

 

from control to

 

 

thermostat. Check

 

 

operation.

TECHNICAL HELP

1G

Is 120V

present across

control terminals YES LINE & LINE NEUTRAL?

NO

Correct 120V

power supply. Check

operation.

1H NO

Is 120V

present at YES control terminals

XFMR & XFMR

NEUTRAL?

1I

 

1J

 

1K

 

Is 120V

 

Is 24V

 

Is 24V

 

 

 

present

 

present across

YES

present across

YES

across 12-pin

 

primary of control

 

secondary of

 

connector pins TH

YES

transformer?

 

transformer?

 

& TR on the

 

 

 

 

control?

 

NO

 

NO

 

NO

 

Repair wiring to

 

Replace

 

Repair wiring

 

 

 

and/or plug

 

transformer. Check

 

transformer. Check

 

 

 

 

connection. Check

 

operation.

 

operation.

 

 

 

 

operation.

 

 

 

 

 

 

!WARNING

If diagnostic indicator (LED)

shows continuous flashing, turn off gas supply at source before disconnecting electrical power!