Emerson 7000 manual Troubleshooting for MV ACTS, 3-2Troubleshooting, Danger, 381333-395, Problem

Models: 7000

1 12
Download 12 pages 23.06 Kb
Page 10
Image 10
3-2 Troubleshooting

3-2 Troubleshooting

381333-395

Troubleshooting for MV ACTS

!DANGER

Refer to the Group 5 Controller User’s Guide 381333-126for ATS status display messages, time delays, pickup & dropout settings, & adjustments.

Hazardous voltage capable of causing shock, burns, or death is used in the switch. Do not touch the power or load terminal of the transfer switch!

Problem

Check in Numerical Sequence

 

1 Operation

2 Gen-Set

3 Voltage on

 

Display

 

 

 

 

 

Starting control must be in

 

Gen-Set does not start

Hold Transfer Test switch 15

the automatic position.

 

Batteries must be charged

 

when the Transfer

seconds or the outage must be

and connected. Check

 

Control switch is turned

long enough to allow for

wiring to engine starting

 

and held in Transfer Test

Feature 1C time delay plus

contacts on customer

 

position or when the

engine cranking and starting

terminal block TB. Verify on

 

normal source fails.

time.

the controller that small

 

 

 

plug J3 is connected to

 

 

 

receptacle P3.

 

 

 

 

Emergency

Transfer switch does not

 

Generator output circuit

voltage on

transfer the load to the

Wait for Feature 2B time delay

breaker must be closed.

controller display

emergency source after

Generator frequency must

should read at

to time out (if used).

the engine-generator set

be at least 95% of nominal

least 90% of

 

starts.

 

(57 Hz for a 60 Hz system.)

nominal phase to

 

 

 

phase voltage.

Transfer switch does not

 

 

Normal voltage on

transfer the load to

 

 

controller display

normal source when

Wait for Feature 3A time delay

 

should read at

normal returns or when

to time out (if used).

 

least 90% of

the Transfer Control

 

 

nominal phase to

switch is released.

 

 

phase voltage.

Engine-generator set

 

 

 

does not stop after load

Wait for Feature 2E time delay

Starting control must be in

 

retransfer to the normal

to time out (if used).

the automatic position.

 

source.

 

 

 

Failure to Synchronize

Conditions of normal or emergency

sources not suitable for closed transition

light comes on.

transfer. Recheck voltage and frequency of both sources. Press Alarm Reset.

Extended Parallel Time

CBN and CBE contacts are closed longer than setting in the controller. Open the

light comes on.

disconnected source CB, then call ASI for assistance.

 

TS Locked Out light

Transfer lockout operation has occurred; transfer switch is disabled from automatic

comes on.

operation. Open the disconnected source circuit breaker, then call ASI.

Circuit breaker trips (on

Check the controller display for error messages and determine the cause of the

trip. After the fault is cleared, turn the Breaker Control switch to CLOSE. Press

an ATS without protective

the Alarm Reset button.

 

 

relay)

 

 

The CB should close.

 

 

 

 

 

Circuit breaker trips (on

Check the protective relay and determine the cause of the trip (refer to device’s

instructions). After fault is cleared, reset the protective relay. Then reset the Lock-

an ATS with a protective

Out Relay by turning it to RESET. Next turn the Breaker Control switch to

relay)

CLOSE. Press the Alarm Reset button.

 

 

The CB should close.

 

 

Page 10
Image 10
Emerson 7000 Troubleshooting for MV ACTS, 3-2Troubleshooting, Danger, 381333-395, Problem, Check in Numerical Sequence