Troubleshooting |
Troubleshooting for MV ADTS
!DANGER
Refer to the Group 5 Controller User’s Guide
Hazardous voltage capable of causing shock, burns, or death is used in the switch. Do not touch the power or load terminal of the transfer switch!
Problem | Check in Numerical Sequence |
| ||
1 Operation | 2 | 3 Voltage on | ||
| Display | |||
|
|
| ||
|
| Starting control must be in |
| |
Hold Transfer Test switch 15 | the automatic position. |
| ||
Batteries must be charged |
| |||
when the Transfer | seconds or the outage must | and connected. Check |
| |
Control switch is turned | be long enough to allow for | wiring to engine starting |
| |
and held in Transfer Test | Feature 1C time delay plus | contacts on customer |
| |
position or when the | engine cranking and starting | terminal block TB. Verify on |
| |
normal source fails. | time. | the controller that small |
| |
|
| plug J3 is connected to |
| |
|
| receptacle P3. |
| |
|
|
| Emergency | |
Transfer switch does not |
| Generator output circuit | voltage on | |
transfer the load to the | Wait for Feature 2B time | breaker must be closed. | controller display | |
emergency source after | Generator frequency must | should read at | ||
delay to time out (if used). | ||||
the | be at least 95% of nominal | least 90% of | ||
| ||||
starts. |
| (57 Hz for a 60 Hz system.) | nominal phase to | |
|
|
| phase voltage. | |
Transfer switch does not |
|
| Normal voltage on | |
transfer the load to normal |
|
| controller display | |
source when normal | Wait for Feature 3A time |
| should read at | |
returns or when the | delay to time out (if used). |
| least 90% of | |
Transfer Control switch is |
|
| nominal phase to | |
released. |
|
| phase voltage. | |
|
|
| ||
not stop after load | Wait for Feature 2E time | Starting control must be in |
| |
retransfer to the normal | delay to time out (if used). | the automatic position. |
| |
source. |
|
|
| |
Load Disconnect Active | Wait for load disconnect time | Explanation: Transfer switch | in | |
transfer mode. Load disconnect time delay is | ||||
light comes on. | delay to time out. | |||
adjustable from 0 to 5 min. 59 sec. | ||||
|
| |||
Load Disconnect Active | Check load disconnect time | Explanation: Transfer switch contacts are open | ||
light stays on longer than 6 | longer than 5 min. 59 sec (maximum setting). | |||
delay setting. Call ASI. | ||||
min.. | Load remains disconnected. |
| ||
|
| |||
Circuit breaker trips (on an | Check the controller display for | error messages and determine the cause of the | ||
trip. After the fault is cleared, turn the Breaker Control switch to CLOSE. Press | ||||
ATS without protective | ||||
the Alarm Reset button. |
|
| ||
relay) |
|
| ||
The CB should close. |
|
| ||
|
|
| ||
| Check the protective relay and determine the cause of the trip (refer to device’s | |||
Circuit breaker trips (on an | instructions). After fault is cleared, reset the protective relay. Then reset the | |||
ATS with a protective | ||||
relay) | CLOSE. Press the Alarm Reset button. |
| ||
| The CB should close. |
|
|