Note: The complete range of options is displayed, regardless of the duty selected earlier.
e)Once the desired profile is shown (flashing) on the display, press the blue button → to select this option. It will now stop flashing.
f)If the chosen profile is incorrect, the edit sequence for the profile selection can be
If the profile is correct, press the red button ↵ to save the profile to memory and automatically scroll on to the next main menu option.
Note:
The next menu item presented will depend upon the flow profile chosen :-
i)3/2 5/2 : the next menu item will be “SCALE”
The MSP400 will automatically calculate the Power factor and only requies the K factor to be entered.
Refer to section 4.4.6
ii)Manning : the next menu item will be “LEUEL @ max”. Refer to section 4.4.7.
iii)Parshall, FF or FP : the next menu item will be “d”. The MSP400 will automatically calculate the appropriate Power factor and K factor, and will set the 4mA point at zero flow and the 20mA point at maximum flow.
Refer to section 4.4.12.
4.4.4.2 Contents measurement
Lin | Linear (factory default setting) |
H.CYL.F | Horizontal cylinder on it’s side with flat ends |
SPH. | Spherical vessel |
H.CYL.D | Horizontal cylinder on it’s side with dished ends |
To change the contents profile:
a)Press the green button ↓ to display the “ProF” menu entry screen.
b)Press the blue button → to display the current selection. If this selection is correct, press the red button ↵ to return to the main menu.
c)To change the profile to one of the other options, press the blue button → to enter the “ProF” menu. The current selection will now be flashing, indicating it may be changed.
d)Press the green button ↓ to scroll through the list of available profile options, as given in the table above.
Note: The complete range of options is displayed, regardless of the duty selected earlier.
e)Once the desired profile is shown (flashing) on the display, press the blue button → to select this option. It will now stop flashing.
f)If the chosen profile is incorrect, the edit sequence for the profile selection can be
If the profile chosen is “Lin”, press the red button ↵ to save the profile to memory and automatically scroll on to the next main menu option “SCALE”.
Refer to section 4.4.6.