Reliable UPS Protection And Extended Battery Time To Keep Your Network Up And Running

The flexible design of Liebert PSI-XR allows the unit to be configured as a self-standing tower or to be rack-mounted within a 2U space. It is available in four capacities, and both 120V or 230V models.

The UPS features an innovative line-interactive design incorporating buck/boost automatic voltage regulation technology. This protects against utility voltage fluctuation by raising and lowering utility power to the level needed by the connected equipment. It also allows the UPS to prolong battery life by maximizing its time on utility power before going to battery.

Liebert PSI-XR Standard Features:

Flexibility:

Six to seven battery-backed outlets

Allows the Liebert PSI-XR to be more flexible in accommodating additional equipment to be connected to the UPS via the 15, 20 or 30 Amp receptacles.

Configurable input voltage window

Allows the UPS to be properly matched to the incoming utility power and adjusts its input window and transfer points to supply precisely regulated power to connected loads within the selected range. Also enables the UPS to meet the required input voltage when transferring to battery.

Rotatable Display Panel

90 degrees rotatable LED display panel rotates 90° to make the readout of the LED display easy to see in rack or tower position.

Automatic Frequency Sensing

The UPS automatically adjusts to the input frequency, 50Hz or 60Hz.

Rack Rail Kit

These telescoping rails mount to the sides of the UPS to facilitate installation into a rackmount enclosure.

Battery Runtime Chart

(Runtimes are in minutes, assuming fully charged batteries at 25°C)

Number of batteries

Load %

1000VA

1500VA

2200VA

3000VA

Internal battery

50

15

13

14

13

 

100

6

5

5

5

Internal Battery +1

50

73

55

45

31

External Battery Cabinet

100

31

18

15

12

Internal Battery + 2

50

129

95

67

56

External Battery Cabinets

100

65

46

29

18

Internal Battery + 3

50

181

131

95

73

External Battery Cabinets

100

96

64

48

31

Internal Battery + 4

50

233

167

143

95

External Battery Cabinets

100

124

82

72

47

Internal Battery + 5

50

285

203

167

113

External Battery Cabinets

100

151

106

84

56

Internal Battery + 6

50

336

239

191

131

External Battery Cabinets

 

 

 

 

 

100

179

124

102

65

Optional external battery cabinets

Provide extended runtime for applications that require longer backup time.

UPS with internal battery

RS232

Liebert

Input

Output

 

(DB-9)

Intellislot

Circuit

Circuit

 

Port

Port

Breakers

Breakers

Receptacles

Voltage

EPOUSB

RJ-45

External

Power

Configuration

Port

Data Line

Battery

Cord

DIP Switch

 

Connectors

Connector

 

Optional External Battery Cabinet

Add up to 6 cabinets for additional runtime

2

Page 2
Image 2
Emerson PSI-XR manual Flexibility, Configurable input voltage window