Installation Instructions
1.Please fully read these instructions prior to installation and operation.
2.Determine a suitable mounting location for the SL‑2G control. The control must be placed in a location that is within 4’ of a 120VAC electrical outlet and within 8’ of the pipe being heated and controlled.
3.Mount the
4.The
5.Carefully uncoil and straighten the sensing wire/sensing bulb and attach it to the outer surface of the pipe being heated. The bulb on the end of the sensing wire must be located in an area that is experiencing the same freezing or damaging cold temperatures that the pipe is experiencing. The sensing wire must not be kinked or compressed during installation. When used with the ILH product, the sensing wire must be secured to piping with tape, and not with devices such as cable ties or pipe clamps, as these will damage the sensing wire. The sensing wire must be protected from damage. Sensing wire damage will result in improper control of the heating cables and may result in frozen pipes and the risk of fire or electrical shock.
6.Plug the SL‑2G power cordset into a 120 VAC receptacle.
The lighted plug on the cordset will illuminate indicating that there is power being supplied to the SL‑2G control. Turn the
SL‑2G control knob to the maximum setting of 25°C (77°F).
The GFCI receptacle indicator light should be off. If the GFCI receptacle indicator light is illuminated press the “Reset” button on the receptacle, the GFCI receptacle indicator light should then turn off. If the GFCI cannot be reset, then a fault exists. Do not attempt to bypass the GFCI. Bypassing the GFCI will result in the risk of fire or electrical shock.
7.Set the desired protection temperature for your application by adjusting the control activation temperature between 2° C and 25°C (36°F to 77°F).
8.Plug in your ILH heating cable to the GFCI receptacle on the front of the SL‑2G control.
Power Cord to be hanked
to maximum 4” dia
Neon Light
Clear Plug
9ºC/48ºF
17ºC/63ºF
2ºC/36ºF
F
25ºC/77º
Mounting
Slots
Senseor Wire
Assembly
4ft (from cabinet) CSA type SJT 105°C
Operation Instructions
1.The
2.The bulb on the end of the sensing wire senses the temperature. If the temperature of the bulb drops below the
3.The
4.Disconnect the power to the
5.At the beginning of the heating season and monthly during operation, inspect the
a)If the ambient is below 21°C, turn the thermostat control knob to the maximum setting; the GFCI will be energized. Push the “TEST” button on the GFCI recptacle; a “click” should be heard and the receptacle indicator light will turn on. Push the “RESET” button on the GFCI recptacle to reset the power (the indicator light will turn off).
b)If the ambient temperature is above 22°C, you will need to “cool down” the sensing bulb to test the GFCI. It is recommended to wait until the bulb is below 21°C as in step a), however if this is not possible you will need to submerge the sensing bulb in ice water for 10 minutes and then follow the instructions as described in a) above.
6.The GFCI will not be affected by power interruptions.
7.Discontinue use and remove any unit that has been damaged or has deteriorated for any reason.
8.Other conditions to look for are chewing by animals, water damage/corrosion or physical abuse.