Table 3

Condenser performance, 60Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total Heat Rejection BTU/Hr (kW) Based on TD

 

 

 

Model

 

30°F TD

25°F TD

20°F TD

15°F TD

1°F TD

CFM

Sound

Fan

Number

 

(16.7°C)

(13.9°C)

(11.1°C)

(8.3C)

(0.6°C)

(CMH)

dBA

Qty

R-22 Refrigerant

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TCDV165

 

178,410

148,675

118,940

89,205

5,947

13,300

 

 

 

(52.2)

(43.5)

(34.8)

(26.1)

(3.1)

(22,597)

 

 

 

 

75.5

2

TCDV205

 

264,930

220,775

176,620

132,465

8,831

11,200

 

 

 

 

(77.6)

(64.6)

(51.7)

(38.8)

(4.7)

(19,029)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TCDV251

 

298,170

248,475

198,780

149,085

9,939

20,250

 

 

 

(87.3)

(72.8)

(58.2)

(43.7)

(5.2)

(34,405)

 

 

 

 

77.3

3

TCDV308

 

384,180

320,150

256,120

192,090

12,806

18,600

 

 

 

 

(112.5)

(93.7)

(75.0)

(56.2)

(6.7)

(31,602)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TCDV415

 

507,690

423,075

338,460

253,845

16,923

24,800

 

 

 

(148.7)

(123.9)

(99.1)

(74.3)

(8.9)

(42,135)

 

 

 

 

78.5

4

TCDV510

 

552,240

460,200

368,160

276,120

18,408

19,200

 

 

 

 

(161.7)

(134.8)

(107.8)

(80.9)

(9.7)

(32,621)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R-407C Refrigerant

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TCDV165

 

143,160

119,300

95,440

71,580

4772

13,300

 

 

 

(41.9)

(34.9)

(27.9)

(21.0)

(2.5)

(22,597)

 

 

 

 

75.5

2

TCDV205

 

242,100

201,750

161,400

121,050

8070

11,200

 

 

 

 

(70.9)

(59.1)

(47.3)

(35.4)

(4.3)

(19,029)

 

 

 

 

 

 

TCDV251

 

277,380

231,150

184,920

138,690

9246

20,250

 

 

 

(81.2)

(67.7)

(54.1)

(40.6)

(4.9)

(34,405)

 

 

 

 

77.3

3

TCDV308

 

337,890

281,575

225,260

168,945

11263

18,600

 

 

 

 

(98.9)

(82.4)

(66.0)

(49.5)

(5.9)

(31,602)

 

 

 

 

 

 

TCDV415

 

472,320

393,600

314,880

236,160

15744

24,800

 

 

 

(138.3)

(115.3)

(92.2)

(69.2)

(8.3)

(42,135)

 

 

 

 

78.5

4

TCDV510

 

452,820

377,350

301,880

226,410

15094

19,200

 

 

 

 

(132.6)

(110.5)

(88.4)

(66.3)

(8.0)

(32,621)

 

 

 

 

 

 