Dimensional and Electrical Data

2.0DIMENSIONAL AND ELECTRICAL DATA

Figure 3 Cabinet and anchor dimensional data—VFD control condensers, 50 and 60Hz

Eyebolts for lifting condenser

Provided on four-fan models only

A

43-9/16"

 

(1107mm)

 

 

 

37-7/8" (962mm)

18" (457mm)

Height to top of fan guard:

43-1/8" (1095mm)

Disconnect

43-3/16"Switch

(1097mm)

Cabinet Dimensions

 

B

C D

Clearance of36" (914.4mm) on all sides is recommended for proper operation and component access

4 legs furnished for 2- and 3-fan

 

 

 

 

models

37-11/16"

6 legs furnished for 4-fan models

(957mm)

Unit Anchor Plan

1-7/8” (47.6mm)

4-1/4”

(108mm)

Typical Diameter 9/16" (14.3mm)

1-7/8” (47.6mm)

4-1/4” (108mm)

Typical Footprint

1-3/4”

(44.5mm)

1-3/4”

1”

(44.5mm)

(25.4mm)

DPN001049

Rev. 0

Table 5

Physical data—VFD control condensers, 50 and 60Hz

 

 

 

 

 

 

 

 

 

 

 

 

Number

A

B

C

D

Net Weight

 

 

 

 

 

 

 

Model #

 

of Fans

in (mm)

in (mm)

in (mm)

in (mm)

lb (kg)

 

 

 

 

 

 

 

 

TCDV165

 

2

91-1/2 (2324)

84 (2134)

82 (2083)

--

425 (193)

 

 

 

 

 

 

 

 

TCDV205

 

2

91-1/2 (2324)

84 (2134)

82 (2083)

--

495 (225)

 

 

 

 

 

 

 

 

TCDV251

 

3

131-1/2 (3340)

124 (3150)

122 (3099)

--

500 (227)

 

 

 

 

 

 

 

 

TCDV308

 

3

131-1/2 (3340)

124 (3150)

122 (3099)

--

670 (305)

 

 

 

 

 

 

 

 

TCDV415

 

4

171-1/2 (4356)

164 (4166)

82 (2083)

80 (2032)

815 (370)

 

 

 

 

 

 

 

 

TCDV510

 

4

171-1/2 (4356)

164 (4166)

82 (2083)

80 (2032)

1188 (540)

 

 

 

 

 

 

 

 

All condenser fan motors are 3/4 hp

5

Page 9
Image 9
Emerson TCDVTM manual Unit Anchor Plan, Physical data-VFD control condensers, 50 and 60Hz, Typical Footprint