Guide Specifications
3.0GUIDE SPECIFICATIONS
3.1General
Each condenser shall consist of housing, condenser coil, propeller fans
_____volt,
3.2Coil
Liebert manufactured coil shall be constructed of copper tubes in a staggered tube pattern. Tubes are expanded into continuous, corrugated aluminum fins. The fins have full depth fin collars completely covering the copper tubes, which are connected to heavy wall Type "L" headers. Inlet coil connector tubes pass through relieved holes in the tube sheet for maximum resistance to piping strain and vibration. Coils are factory
3.3Fans
Fans shall have aluminum blades secured to corrosion protected steel hubs. Fans shall be secured to the fan shaft by means of a
3.4Fan Motors
The variable speed fan motor shall be an inverter duty motor with permanently lubricated ceramic bearings. The Liebert variable frequency drive control system shall provide overload protection for the variable speed motor. Each
3.5Head Pressure Control
The Liebert VFD Condenser control system shall include a variable frequency drive, inverter duty fan motor operating from 0% to 100% motor RPM based on head pressure, refrigerant pressure transduc- ers,
3.6Housing
The condenser housing shall be constructed of bright aluminum sheet and divided into individual fan sections by full width baffles. Structural support members, including coil support frame, motor and drive support, are galvanized steel for strength and corrosion resistance. Aluminum legs are provided with rigging holes for hoisting the unit into position.
3.7TVSS and Unit Disconnect Switch
Transient Voltage Surge Suppression and locking disconnect shall be
3.8Alarm Contacts
Normally open, dry contacts shall be provided for indication of VFD and TVSS alarm condition.
3.9Electrical Controls
All electrical connections and controls shall be provided in a weatherproof enclosure. The enclosure shall be integral with the condenser for pleasing appearance as well as functional protection.
7