EC2-352 Display Case and Coldroom Controller
Operating Instructions
GB
Note: This document contains short form instructions for experienced users. Use last column in List of Parameters to document your individual settings. More detailed information can be found in the User Manual.
The
Network
6 | 4 |
|
8 | 5 | 1 |
| ||
|
| 2 |
9 | 3 |
|
|
| |
7 |
|
|
A PT5 pressure transmitter (1) and an
In case of power loss, due to the positive
!Safety instructions:
•Read installation instructions thoroughly. Failure to comply can result in device failure, system damage or personal injury.
•The product is intended for use by persons having the appropriate knowledge and skills.
•Ensure electrical ratings per technical data are not exceeded.
•Disconnect all voltages from system before installation.
•Keep temperatures within nominal limits.
•Comply with local electrical regulations when wiring
Technical Data
EC2 Series Controller
Power supply |
| 24VAC ±10%; 50/60Hz; Class II |
Power consumption |
| 20VA max including EX2 |
Communication |
| TCP/IP Ethernet 10MBit/s |
| Removable screw terminals | |
|
| wire size 0.14 … 1.5 mm2 |
Temperature |
|
|
storage |
| |
operating |
| 0 … +60°C |
Humidity |
| 0…80% r.h. non condensing |
Protection class |
| IP65 (front protection with gasket) |
Pressure transmitter input | 24VDC, 4...20mA | |
Output relays | (3) | SPDT contacts, AgCdO |
|
| Inductive (AC15) 250V/2A |
|
| Resistive (AC1) 250V/8A; 12A total return current |
Triac output for EX2 |
| 24V AC, 0.1 … 1A |
Electrical Control Valve |
| |
Coil (ASC 24V only) |
|
|
Marking |
|
|
|
|
|
Mounting
The
Push controller into panel cutout.(1)
Make sure that mounting lugs are flush with outside of controller housing
Insert allen key into front panel holes and turn clockwise. Mounting lugs will turn and gradually move towards panel (2)
Turn allen key until mounting lug barely touches panel. Then move other mounting lug to the same position (3)
Tighten both sides very carefully until controller is secured. Do not over tighten as mounting lugs will break easily.
Electrical Installation
Refer to the electrical wiring diagram (below) for electrical connections. A copy of this diagram is labeled on the controller. Use connection wires/cables suitable for 90°C operation (EN
EC2 analog inputs are for dedicated sensors only and should not be connected to any other devices. Connecting any EC2 inputs to mains voltage will permanently damage the EC2.
Important: Keep controller and sensor wiring well separated from mains wiring. Minimum recommended distance 30mm.
Warning: Use a class II category transformer for 24VAC power supply (EN 60742). Do not ground the 24VAC lines. We recommend to use one transformer per EC2 controller and to use separate transformers for 3rd party controllers, to avoid possible interference or grounding problems in the power supply. Connecting any EC2 inputs to mains voltage will permanently damage the EC2.
Replacement for Rev.:04 | 1 / 4 | PCN : 864 925 16.09.2009 |