EC2-352 Display Case and Coldroom Controller

Operating Instructions

GB

List Of Parameters

/

DISPLAY PARAMETERS

 

Min

 

Max

Unit

 

Def.

Custom

/1

Value to show

 

 

0

 

9

-

 

0

 

 

 

0

= Thermostat control temperature with Temp. alignment /C

 

 

 

 

1

= Air-in temperature °C

 

 

 

 

 

 

 

 

 

2

= Air-out temperature °C

 

 

 

 

 

 

 

 

 

3

= Alarm temperature °C

 

 

 

 

 

 

 

 

 

4

= Defrost termination temperature °C

 

 

 

 

 

 

 

 

 

5

= Coil-in temperature °C calculated from the pressure

 

 

 

 

6

= Coil-out temperature °C

 

 

 

 

 

 

 

 

 

7

= Calculated superheat °K

 

 

 

 

 

 

 

 

 

8

= Valve opening in %

 

 

 

 

 

 

 

 

 

9

= Displays defrost status

 

 

 

 

 

 

 

 

/2

Alarm suppression

0 = off, 1 = on

 

0

 

1

-

 

0

 

 

/5

Temperature Unit

0 = °C, 1 = °F

 

0

 

1

-

 

0

 

 

/6

Decimal point

0 = yes, 1 = no

 

0

 

1

-

 

0

 

 

/7

Display during defrost

 

 

0

 

2

-

 

0

 

 

 

0

= dF (= defrost mode); 1 = dF +

defrost termination temp.

 

 

 

 

 

2 = dF + control temperature

 

 

 

/C

Temperature alignment for /1=0

 

-20

 

20

K / °F

 

0.0

 

 

A

ALARM PARAMETERS

 

 

 

 

 

 

 

 

 

A0

Mean factor alarm temperature

 

0

 

100

%

 

100

 

 

A1

Low temp alarm delay

 

0

 

180

min

 

5

 

 

A2

High temp alarm delay

 

0

 

180

min

 

5

 

 

A3

Alarm delay after defrost

 

0

 

180

min

 

10

 

 

AH

High temp alarm limit

 

 

AL

 

70

°C / K

 

40

 

 

AL

Low temp alarm limit

 

 

-55

 

AH

°C / K

 

-50

 

 

At

Alarm limit type

 

 

0

 

1

-

 

0

 

 

 

0=absolute temperatures °C; 1= relative

temperatures K to setpoint

 

 

r

THERMOSTAT PARAMETERS

 

 

 

 

 

 

 

 

r1

Min setpoint

 

 

-50

 

r2

°C

 

-50

 

 

r2

Setpoint max

 

 

r1

 

60

°C

 

40

 

 

r3

Day/night control

0 = off, 1 = on

 

0

 

1

-

 

1

 

 

r4

Thermostat mode

 

 

0

 

4

-

 

1

 

 

 

0

= off, no thermostat function, continues

cooling air in sensor

 

 

 

 

monitoring off, no temp. alarms generated

 

 

 

 

 

 

 

1

= cooling, deadband control

 

 

 

 

 

 

 

 

 

 

cut in = set-point + difference

 

 

 

 

 

 

 

 

 

 

cut out = set-point

 

 

 

 

 

 

 

 

 

 

 

2

= cooling, modulating thermostat

 

 

 

 

 

 

 

 

 

 

cut in = set-point

 

 

 

 

 

 

 

 

 

 

 

 

cut out = set-point – difference /2

 

 

 

 

 

 

 

 

 

3

= heating, deadband control

 

 

 

 

 

 

 

 

 

 

cut in = set-point – difference

 

 

 

 

 

 

 

 

 

 

cut out = set-point

 

 

 

 

 

 

 

 

 

 

 

4

= on, external control using nvi Valve via SNMP. Air in and air out

 

 

 

sensor monitoring off. Temp. alarms will be generated

 

 

 

r6

Setpoint night

 

 

r1

 

r2

°C

 

4.0

 

 

r7

Differential night

 

 

0.1

 

20.0

K

 

2.0

 

 

r8

Mean factor, day operation

 

0

 

100

%

 

100

 

 

r9

Mean factor, night operation

 

0

 

100

%

 

50

 

 

rd

Differential day

 

 

0.1

 

20.0

K

 

2.0

 

 

St

Setpoint day

 

 

r1

 

r2

°C

 

2.0

 

 

d

DEFROST PARAMETERS

 

 

 

 

 

 

 

 

 

d0

Defrost mode

 

 

0

 

2

-

 

1

 

 

 

0

= natural defrost, defrost heater not

activated

 

 

 

 

 

 

 

 

pulsed defrost not possible

 

 

 

 

 

 

 

 

 

1

= forced defrost, defrost heater activated, pulsed

 

 

 

 

 

 

 

defrost possible

 

 

 

 

 

 

 

 

 

 

 

2

= forced defrost, defrost heater activated, pulsed defrost possible,

 

 

 

defrost termination using nviStartUp via SNMP

 

 

 

 

 

d1

Termination by:

 

 

0

 

3

-

 

0

 

 

 

0

= termination by temperature,

 

 

 

 

 

 

 

 

 

 

 

termination by time will generate an alarm

 

 

 

 

 

 

1

= termination by time,

 

 

 

 

 

 

 

 

 

 

termination by temperature will generate an alarm

 

 

 

 

2

= first, what ever comes first time or temperature, no alarm

 

 

 

 

3

= last, by time and temperature, no alarm

 

 

 

 

 

 

d2

Defrost termination sensor

 

0

 

1

-

 

1

 

 

 

0

= Dedicated defrost sensor must be

installed

 

 

 

 

 

 

 

 

1

= Air-out sensor used for defrost termination

 

 

 

 

 

EC2-352_65117_EN_R05.doc

Replacement for Rev.:04

 

 

 

 

 

 

Min

Max

Unit

 

Def.

Custom

d3

Pulsed defrost

 

 

0

1

-

 

0

 

 

 

0

= off, no pulsed defrost, heaters switched off at defrost termination

 

 

 

 

temperature dt or max. time dP whatever is selected

 

 

 

 

1

= on, pulsed defrost, dd and dH in use, heaters are switched off at

 

 

 

dH and switched on again at dH – dd

 

 

 

 

 

 

d4

Defrost at startup

0 = no, 1 = yes

0

1

-

 

0

 

 

d5

Delay power up defrost

 

0

180

min

 

0

 

 

d6

Pump down delay

 

 

0

180

sec

 

0

 

 

 

Compressor will run during pump down

delay

while

valve is

closed

 

 

d7

Drain delay

 

 

 

0

15

min

 

2

 

 

d8

Injection delay

 

 

0

180

sec

 

0

 

 

 

Valve is open during injection delay while compressor is not running

 

 

d9

Demand defrost mode

 

 

0

2

-

 

0

 

 

 

0

= off, 1 = on, 2 = on together with

 

 

 

 

 

 

 

 

timed defrost

 

 

 

 

 

 

 

 

 

dd

Pulsed defrost differential

1

20

K

 

2

 

 

dH

Pulsed defrost setpoint

 

-40

dt

°C

 

5

 

 

dt

Defrost termination temperature

-40

90

°C

 

8

 

 

dP

Max defrost duration

 

 

0

180

min

 

30

 

 

dI

Defrost interval

 

 

0

192

h

 

8

 

 

du

Start up delay after synch

0

180

min

 

30

 

 

F

FAN PARAMETERS

 

 

 

 

 

 

 

 

F1

Fan startup by: 0 = on

 

0

4

-

 

0

 

 

 

1

= delayed by time Fd, error on temperature

 

 

 

 

 

 

 

2

= by temperature Ft, error on time

 

 

 

 

 

 

 

 

3

= first, whatever comes first time or temperature, no alarm

 

 

 

 

4

= last, time and temperature must come, no alarm

 

 

 

 

 

F2

During no cooling

 

 

0

2

-

 

0

 

 

 

0

= on; 1 = off; 2 = delayed by F4; 3 =

off, when door open

 

 

 

F3

During defrost

0 = on, 1 = off

0

1

-

 

0

 

 

F4

Stop delay time

 

 

0

30

min

 

0

 

 

F5

During cleaning

0 = off, 1 = on

0

1

-

 

0

 

 

Fd

Fan delay after defrost

 

0

30

min

 

0

 

 

Ft

On temp after defrost

 

 

-40

40

°C

 

0

 

 

C

COMPRESSOR PARAMETERS

 

 

 

 

 

 

 

C0

Delay first start after power up

0

15

min

 

0

 

 

C1

Cycle time

 

 

 

0

15

min

 

0

 

 

C2

Min. stop time

 

 

0

15

min

 

0

 

 

C3

Min. run time

 

 

0

15

min

 

0

 

 

u

SUPERHEAT PARAMETERS

 

 

 

 

 

 

 

u0

Refrigerant

0 = R22

 

1 = R134a

0

7

-

 

3

 

 

 

2

= R507 3 = R404A

4 = R407C

 

 

 

 

 

 

 

 

5

= R410A

6 = R124

 

7 = R744

 

 

 

 

 

 

 

u1

Correction glide / dp

 

 

-20.0

20.0

K

 

0.0

 

 

 

Glide

= positive

values

 

 

 

 

 

 

 

 

Pressure drop = negative values

 

 

 

 

 

 

 

u2

MOP control

 

 

0

1

-

 

0

 

 

 

0

= MOP off, 1 = MOP on

 

 

 

 

 

 

 

u3

MOP temperature

 

 

-40

40

°C

 

0

 

 

u4

Superheat mode

0 = off

0

2

-

 

1

 

 

 

1

= fixed superheat

 

 

 

 

 

 

 

 

 

 

2

= adaptive superheat

 

 

 

 

 

 

 

 

u5

Superheat init setpoint

 

 

u6

u7

K

 

6

 

 

u6

Superheat setpoint min.

 

3

u7

K

 

3

 

 

u7

Superheat setpoint max.

 

u6

20

K

 

15

 

 

uu

Start opening

 

 

25

75

%

 

30

 

 

P

ANALOG SENSOR PARAMETERS

 

 

 

 

 

 

 

P1

Pressure sensor type selection

0

2

-

 

0

 

 

 

0

= PT5-07M; 1 = PT5-18M; 2 = PT5-

30M

 

 

 

 

 

 

H

OTHER PARAMETERS

 

 

 

 

 

 

 

H2

Display access

 

 

0

4

-

 

3

 

 

 

0

= all disabled (Caution, access to controller only via the TCP/IP

Ethernet

 

 

 

network possible)

 

 

 

 

 

 

 

 

 

 

1

= Keyboard enabled

 

 

 

 

 

 

 

 

 

 

2

= IR remote control enabled

 

 

 

 

 

 

 

 

3

= Keyboard and IR remote control; Temporary data display and manual

 

 

 

defrost enabled.

 

 

 

 

 

 

 

 

 

 

4

= Keyboard and IR remote control; Temporary data display disabled.

 

 

 

Control setpoint with SEL key and manual defrost enabled.

 

H3

IR access code

 

 

0

199

-

 

0

 

 

H5

Password

 

 

 

0

199

-

 

12

 

 

 

 

3 / 4

 

 

 

PCN : 864 925

16.09.2009

 

Page 3
Image 3
Emerson Process Management EC2-352 user manual List Of Parameters, Min Max Unit Def

EC2-352 specifications

Emerson Process Management has consistently been at the forefront of industrial automation and process control technologies, and the EC2-352 is a testament to their commitment to innovation and excellence. This device is part of Emerson's broader portfolio aimed at improving operational efficiency, reliability, and safety in various process environments.

The EC2-352 is designed as a robust and flexible platform for monitoring and control applications. One of its main features is its adaptability to a wide variety of environments, making it suitable for diverse industries including oil and gas, chemicals, pharmaceuticals, and food processing. This versatility is underpinned by its ability to connect seamlessly with existing systems and equipment.

One of the defining technologies integrated into the EC2-352 is its advanced communication capabilities. It supports multiple communication protocols such as HART, MODBUS, and Ethernet/IP, facilitating easy integration with both legacy and modern systems. This ensures that users can maintain a high level of interoperability in their operations.

The device is equipped with a powerful processing engine, which allows for real-time data acquisition and analysis. This feature is essential for making informed decisions based on the latest information, ultimately leading to improved operational performance. Additionally, the EC2-352 offers built-in diagnostics and predictive maintenance capabilities. These tools not only enhance reliability but also extend the lifecycle of equipment by proactively addressing potential issues before they become critical.

Another significant characteristic of the EC2-352 is its user-friendly interface. With intuitive controls and a clear display, operators can easily configure settings and monitor system performance. This user-centric design minimizes training time and mitigates the risk of operator error.

Moreover, the EC2-352 is built with rugged durability in mind. Its construction is optimized for harsh environmental conditions, ensuring consistent performance even in extreme temperatures or challenging operational scenarios. This resilience translates to lower maintenance costs and decreased downtime.

In conclusion, the Emerson Process Management EC2-352 exemplifies the evolution of process control technology. Through its advanced features, robust processing capabilities, and comprehensive communication options, it stands out as a vital tool for industries seeking to enhance their operational efficiency and reliability. With the EC2-352, Emerson continues to lead the way in delivering solutions that meet the demands of modern industrial environments.