Emerson Process Management EC2-352 user manual List Of Parameters, Unit

Models: EC2-352

1 4
Download 4 pages 14.68 Kb
Page 3
Image 3
List Of Parameters

EC2-352 Display Case and Coldroom Controller

Operating Instructions

GB

List Of Parameters

/

DISPLAY PARAMETERS

 

Min

 

Max

Unit

 

Def.

Custom

/1

Value to show

 

 

0

 

9

-

 

0

 

 

 

0

= Thermostat control temperature with Temp. alignment /C

 

 

 

 

1

= Air-in temperature °C

 

 

 

 

 

 

 

 

 

2

= Air-out temperature °C

 

 

 

 

 

 

 

 

 

3

= Alarm temperature °C

 

 

 

 

 

 

 

 

 

4

= Defrost termination temperature °C

 

 

 

 

 

 

 

 

 

5

= Coil-in temperature °C calculated from the pressure

 

 

 

 

6

= Coil-out temperature °C

 

 

 

 

 

 

 

 

 

7

= Calculated superheat °K

 

 

 

 

 

 

 

 

 

8

= Valve opening in %

 

 

 

 

 

 

 

 

 

9

= Displays defrost status

 

 

 

 

 

 

 

 

/2

Alarm suppression

0 = off, 1 = on

 

0

 

1

-

 

0

 

 

/5

Temperature Unit

0 = °C, 1 = °F

 

0

 

1

-

 

0

 

 

/6

Decimal point

0 = yes, 1 = no

 

0

 

1

-

 

0

 

 

/7

Display during defrost

 

 

0

 

2

-

 

0

 

 

 

0

= dF (= defrost mode); 1 = dF +

defrost termination temp.

 

 

 

 

 

2 = dF + control temperature

 

 

 

/C

Temperature alignment for /1=0

 

-20

 

20

K / °F

 

0.0

 

 

A

ALARM PARAMETERS

 

 

 

 

 

 

 

 

 

A0

Mean factor alarm temperature

 

0

 

100

%

 

100

 

 

A1

Low temp alarm delay

 

0

 

180

min

 

5

 

 

A2

High temp alarm delay

 

0

 

180

min

 

5

 

 

A3

Alarm delay after defrost

 

0

 

180

min

 

10

 

 

AH

High temp alarm limit

 

 

AL

 

70

°C / K

 

40

 

 

AL

Low temp alarm limit

 

 

-55

 

AH

°C / K

 

-50

 

 

At

Alarm limit type

 

 

0

 

1

-

 

0

 

 

 

0=absolute temperatures °C; 1= relative

temperatures K to setpoint

 

 

r

THERMOSTAT PARAMETERS

 

 

 

 

 

 

 

 

r1

Min setpoint

 

 

-50

 

r2

°C

 

-50

 

 

r2

Setpoint max

 

 

r1

 

60

°C

 

40

 

 

r3

Day/night control

0 = off, 1 = on

 

0

 

1

-

 

1

 

 

r4

Thermostat mode

 

 

0

 

4

-

 

1

 

 

 

0

= off, no thermostat function, continues

cooling air in sensor

 

 

 

 

monitoring off, no temp. alarms generated

 

 

 

 

 

 

 

1

= cooling, deadband control

 

 

 

 

 

 

 

 

 

 

cut in = set-point + difference

 

 

 

 

 

 

 

 

 

 

cut out = set-point

 

 

 

 

 

 

 

 

 

 

 

2

= cooling, modulating thermostat

 

 

 

 

 

 

 

 

 

 

cut in = set-point

 

 

 

 

 

 

 

 

 

 

 

 

cut out = set-point – difference /2

 

 

 

 

 

 

 

 

 

3

= heating, deadband control

 

 

 

 

 

 

 

 

 

 

cut in = set-point – difference

 

 

 

 

 

 

 

 

 

 

cut out = set-point

 

 

 

 

 

 

 

 

 

 

 

4

= on, external control using nvi Valve via SNMP. Air in and air out

 

 

 

sensor monitoring off. Temp. alarms will be generated

 

 

 

r6

Setpoint night

 

 

r1

 

r2

°C

 

4.0

 

 

r7

Differential night

 

 

0.1

 

20.0

K

 

2.0

 

 

r8

Mean factor, day operation

 

0

 

100

%

 

100

 

 

r9

Mean factor, night operation

 

0

 

100

%

 

50

 

 

rd

Differential day

 

 

0.1

 

20.0

K

 

2.0

 

 

St

Setpoint day

 

 

r1

 

r2

°C

 

2.0

 

 

d

DEFROST PARAMETERS

 

 

 

 

 

 

 

 

 

d0

Defrost mode

 

 

0

 

2

-

 

1

 

 

 

0

= natural defrost, defrost heater not

activated

 

 

 

 

 

 

 

 

pulsed defrost not possible

 

 

 

 

 

 

 

 

 

1

= forced defrost, defrost heater activated, pulsed

 

 

 

 

 

 

 

defrost possible

 

 

 

 

 

 

 

 

 

 

 

2

= forced defrost, defrost heater activated, pulsed defrost possible,

 

 

 

defrost termination using nviStartUp via SNMP

 

 

 

 

 

d1

Termination by:

 

 

0

 

3

-

 

0

 

 

 

0

= termination by temperature,

 

 

 

 

 

 

 

 

 

 

 

termination by time will generate an alarm

 

 

 

 

 

 

1

= termination by time,

 

 

 

 

 

 

 

 

 

 

termination by temperature will generate an alarm

 

 

 

 

2

= first, what ever comes first time or temperature, no alarm

 

 

 

 

3

= last, by time and temperature, no alarm

 

 

 

 

 

 

d2

Defrost termination sensor

 

0

 

1

-

 

1

 

 

 

0

= Dedicated defrost sensor must be

installed

 

 

 

 

 

 

 

 

1

= Air-out sensor used for defrost termination

 

 

 

 

 

EC2-352_65117_EN_R05.doc

Replacement for Rev.:04

 

 

 

 

 

 

Min

Max

Unit

 

Def.

Custom

d3

Pulsed defrost

 

 

0

1

-

 

0

 

 

 

0

= off, no pulsed defrost, heaters switched off at defrost termination

 

 

 

 

temperature dt or max. time dP whatever is selected

 

 

 

 

1

= on, pulsed defrost, dd and dH in use, heaters are switched off at

 

 

 

dH and switched on again at dH – dd

 

 

 

 

 

 

d4

Defrost at startup

0 = no, 1 = yes

0

1

-

 

0

 

 

d5

Delay power up defrost

 

0

180

min

 

0

 

 

d6

Pump down delay

 

 

0

180

sec

 

0

 

 

 

Compressor will run during pump down

delay

while

valve is

closed

 

 

d7

Drain delay

 

 

 

0

15

min

 

2

 

 

d8

Injection delay

 

 

0

180

sec

 

0

 

 

 

Valve is open during injection delay while compressor is not running

 

 

d9

Demand defrost mode

 

 

0

2

-

 

0

 

 

 

0

= off, 1 = on, 2 = on together with

 

 

 

 

 

 

 

 

timed defrost

 

 

 

 

 

 

 

 

 

dd

Pulsed defrost differential

1

20

K

 

2

 

 

dH

Pulsed defrost setpoint

 

-40

dt

°C

 

5

 

 

dt

Defrost termination temperature

-40

90

°C

 

8

 

 

dP

Max defrost duration

 

 

0

180

min

 

30

 

 

dI

Defrost interval

 

 

0

192

h

 

8

 

 

du

Start up delay after synch

0

180

min

 

30

 

 

F

FAN PARAMETERS

 

 

 

 

 

 

 

 

F1

Fan startup by: 0 = on

 

0

4

-

 

0

 

 

 

1

= delayed by time Fd, error on temperature

 

 

 

 

 

 

 

2

= by temperature Ft, error on time

 

 

 

 

 

 

 

 

3

= first, whatever comes first time or temperature, no alarm

 

 

 

 

4

= last, time and temperature must come, no alarm

 

 

 

 

 

F2

During no cooling

 

 

0

2

-

 

0

 

 

 

0

= on; 1 = off; 2 = delayed by F4; 3 =

off, when door open

 

 

 

F3

During defrost

0 = on, 1 = off

0

1

-

 

0

 

 

F4

Stop delay time

 

 

0

30

min

 

0

 

 

F5

During cleaning

0 = off, 1 = on

0

1

-

 

0

 

 

Fd

Fan delay after defrost

 

0

30

min

 

0

 

 

Ft

On temp after defrost

 

 

-40

40

°C

 

0

 

 

C

COMPRESSOR PARAMETERS

 

 

 

 

 

 

 

C0

Delay first start after power up

0

15

min

 

0

 

 

C1

Cycle time

 

 

 

0

15

min

 

0

 

 

C2

Min. stop time

 

 

0

15

min

 

0

 

 

C3

Min. run time

 

 

0

15

min

 

0

 

 

u

SUPERHEAT PARAMETERS

 

 

 

 

 

 

 

u0

Refrigerant

0 = R22

 

1 = R134a

0

7

-

 

3

 

 

 

2

= R507 3 = R404A

4 = R407C

 

 

 

 

 

 

 

 

5

= R410A

6 = R124

 

7 = R744

 

 

 

 

 

 

 

u1

Correction glide / dp

 

 

-20.0

20.0

K

 

0.0

 

 

 

Glide

= positive

values

 

 

 

 

 

 

 

 

Pressure drop = negative values

 

 

 

 

 

 

 

u2

MOP control

 

 

0

1

-

 

0

 

 

 

0

= MOP off, 1 = MOP on

 

 

 

 

 

 

 

u3

MOP temperature

 

 

-40

40

°C

 

0

 

 

u4

Superheat mode

0 = off

0

2

-

 

1

 

 

 

1

= fixed superheat

 

 

 

 

 

 

 

 

 

 

2

= adaptive superheat

 

 

 

 

 

 

 

 

u5

Superheat init setpoint

 

 

u6

u7

K

 

6

 

 

u6

Superheat setpoint min.

 

3

u7

K

 

3

 

 

u7

Superheat setpoint max.

 

u6

20

K

 

15

 

 

uu

Start opening

 

 

25

75

%

 

30

 

 

P

ANALOG SENSOR PARAMETERS

 

 

 

 

 

 

 

P1

Pressure sensor type selection

0

2

-

 

0

 

 

 

0

= PT5-07M; 1 = PT5-18M; 2 = PT5-

30M

 

 

 

 

 

 

H

OTHER PARAMETERS

 

 

 

 

 

 

 

H2

Display access

 

 

0

4

-

 

3

 

 

 

0

= all disabled (Caution, access to controller only via the TCP/IP

Ethernet

 

 

 

network possible)

 

 

 

 

 

 

 

 

 

 

1

= Keyboard enabled

 

 

 

 

 

 

 

 

 

 

2

= IR remote control enabled

 

 

 

 

 

 

 

 

3

= Keyboard and IR remote control; Temporary data display and manual

 

 

 

defrost enabled.

 

 

 

 

 

 

 

 

 

 

4

= Keyboard and IR remote control; Temporary data display disabled.

 

 

 

Control setpoint with SEL key and manual defrost enabled.

 

H3

IR access code

 

 

0

199

-

 

0

 

 

H5

Password

 

 

 

0

199

-

 

12

 

 

 

 

3 / 4

 

 

 

PCN : 864 925

16.09.2009

 

Page 3
Image 3
Emerson Process Management user manual List Of Parameters, Unit, EC2-352 Display Case and Coldroom Controller