S2H dimensions and specifications
Note: All EMI products are subject to ongoing development programs so design and
specifications may change without notice.
15”
38”
44”
Easy access interconnects on back of unit
1/2” Diameter Lag Holes
3.00”
Front of unit
Electrical
connections | 12.44” |
|
|
|
|
| 4.63” | 28.74” |
| 4.63” |
| ||
|
|
|
|
|
|
|
|
|
|
| |
|
|
| S2H ELECTRICAL SPECIFICATIONS |
|
|
|
| ||||
MODEL |
| FAN | COMPRESSOR 1 | COMPRESSOR 2 | TOTAL | MIN. CIR. | HACR | ||||
VOLTS/HZ/PHASE |
|
|
|
|
|
| AMPS | ||||
RLA | HP | RLA | LRA | RLA | LRA | ||||||
(1) |
| AMPS | (2) | BRKR | |||||||
|
|
|
|
|
|
|
|
|
| ||
9900 | 1.8 | 0.33 | 3.4 | 23 | 3.4 | 23 | 8.6 | 9.5 | 15 | ||
2200 | 1.8 | 0.33 | 4.3 | 27 | 4.3 | 27 | 10.4 | 11.5 | 15 | ||
9200 | 1.8 | 0.33 | 3.4 | 23 | 4.3 | 27 | 9.5 | 10.6 | 15 |
(1)Circuit Designators: 9 = 9,000 Btuh • 2 = 12,000 Btuh (ex. - Model 9200 consists of one 9,000 Btuh compressor and one 12,000 Btuh compressor)
(2)Always refer to the rating plate for Minimum Circuit Ampacity on all multiple compressor units.
S2H PIPING SPECIFICATIONS | Sound Data | Shipping | |||
Model# | Line Sizes | Weight | |||
| |||||
Liquid | Suction | dbA | Lbs. | ||
| |||||
9900 | 1/4” | 1/2” | 64 | 159 | |
2200 | 1/4” | 1/2” | 65 | 197 | |
9200 | 1/4” | 1/2” | 65 | 187 |
S2HA High Capacity Condensing Unit | Made in Rome, New York, USA |