EMI S2H dimensions and specifications, 15” 38” 44”, Amps, S2HA High Capacity Condensing Unit

Models: S2H

1 5
Download 5 pages 25.45 Kb
Page 2
Image 2
S2H dimensions and specifications

S2H dimensions and specifications

Note: All EMI products are subject to ongoing development programs so design and

specifications may change without notice.

15”

38”

44”

Easy access interconnects specifications may change without notice. on back of unit

1/2” Diameter Lag Holes

3.00”

Front of unit

15” Electrical

connections

12.44”

 

 

 

 

 

4.63”

28.74”

 

4.63”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S2H ELECTRICAL SPECIFICATIONS

 

 

 

 

MODEL

 

FAN

COMPRESSOR 1

COMPRESSOR 2

TOTALMIN. CIR.HACR

VOLTS/HZ/PHASE

 

 

 

 

 

 

AMPS

RLA

HP

RLA

LRA

RLA

LRA

(1)

 

AMPS

(2)

BRKR

 

 

 

 

 

 

 

 

 

 

9900

208-230/60/1

1.8

0.33

3.4

23

3.4

23

8.6

9.5

15

2200

208-230/60/1

1.8

0.33

4.3

27

4.3

27

10.4

11.5

15

9200

208-230/60/1

1.8

0.33

3.4

23

4.3

27

9.5

10.6

15

(1)Circuit Designators: 9 = 9,000 Btuh • 2 = 12,000 Btuh (ex. - Model 9200 consists of one 9,000 Btuh compressor and one 12,000 Btuh compressor)

(2)Always refer to the rating plate for Minimum Circuit Ampacity on all multiple compressor units.

S2H PIPING SPECIFICATIONS

Sound Data

Shipping

Model#Line Sizes

Weight

 

Liquid

Suction

dbA

Lbs.

 

9900

1/4”

1/2”

64

159

2200

1/4”

1/2”

65

197

9200

1/4”

1/2”

65

187