Enerco MHIR10LP, TSBF10LP, MHIR20LPT, MHIR30LPT Determining The Type Of Heater Location Space

Models: MHBF20LPT TSIR10LP MHIR30LPT MHIR20LPT TSBF20LPT MHBF10LP MHIR10LP TSBF10LP TSIR20LPT TSBF30LPT TSIR30LPT MHBF30LPT

1 24
Download 24 pages 60.62 Kb
Page 4
Image 4
DETERMINING THE TYPE OF HEATER LOCATION SPACE:

*Adjoining rooms are communication only if there are doorless passageways or ventilation grills between them.

DETERMINING THE TYPE OF HEATER LOCATION SPACE:

Use this method to determine if you have a confined or unconfined space.

Note: the space includes the room in which you install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Find the volume of the space by multiplying room length x width x height.

Example: Space size 18ft (length) x 18ft. (width) x 8ft. (height) = 2592

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to deter- mine the maximum Btu/hr the space can support.

Example: 2592 cu.ft. (volume of space) / 50 cu.ft. = 51.8 or 51,800 (maximum Btu/hr the space can support)

VENTILATION AIR WARNING: If the area in which the heater may be operated in smaller that that defined as an uncon- fined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by on the methods described in the National Fuel Gas Code, NFPA 54/ ANSI Z223.1, Section 5.3 or applicable local codes.

3.Add the Btu/hr of all the fuel-burning appliances in the space such as, Vent–free heater, Gas water heater, Gas furnace, Vented gas heater, Gas fire- place logs, and Other gas appliances*

*Do not include direct-vent gas appliances. Direct- vent draws combustion air from the outdoors and vents to the outdoors.

Example:

 

Gas water heater

40,000 Btu/hr

Vent Free Heater +

20,000 Btu/hr

Total

=60,000 Btu/hr

4.Compare the maximum Btu/hr the space can support with the actual amount of Btu/hr used.

Example: 51,800 Btu/hr (maximum Btu/hr the space can support)

60,000 Btu/hr (Actual amount of Btu/hr used)

The space in the above example is a confined space because the actual Btu/hr used is more than the maximum Btu/hr the space can support.

You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, and the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventila- tion grills between the rooms. See Ventilation Air From Inside Building (Fig. 2)

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors (Fig. 3).

C. Install a lower Btu/hr heater if lower Btu/hr size makes room unconfined.

If actual Btu/hr used is less than the maximum Btu/ hr the space can support, the space is an uncon- fined space. You will need no additional fresh air ventilation.

VENTILATION AIR

Ventilation from Inside Building

This fresh air would come from an adjoining unconfined space. When ventilation to an adjoining unconfined space, you must provide two permanent openings: one within 12” of the ceiling and one within 12” of the floor on the wall connecting the two spaces (see options 1 & 2 of fig. 2). You can also remove door into adjoining room (see option3, fig 2). Follow the National Fuel Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventila- tion grills or ducts.

 

 

12”

Ventilation Or remove

Ventilation Gills into

Adjoining Room -

Gills into

door into

Adjoining

Option 2

Adjoining

Room -

 

 

 

Room -

Option 3

Option 1

 

 

12”

Figure 2

Manual backgroundWARNING: Rework worksheet, adding the space of the adjoining unconfined space. The combined space must have enough fresh air to supply all appliance in both spaces.

4 Installation instructions and Owner’s Manual 70575 Rev. C 8/05

Page 4
Image 4
Enerco MHIR10LP, TSBF10LP Determining The Type Of Heater Location Space, VENTILATION AIR Ventilation from Inside Building