START-UP AND OPERATION
Prior to starting unit for the first time, turn the thermostat system switch to OFF - or raise the cooling setpoint to the highest temperature, to prevent the unit from starting. Close the electrical disconnect switch. This will energize the compressor crankcase heater(s). WAIT A MINIMUM OF FOUR HOURS BEFORE STARTING THE SYSTEM. This period will allow the crankcase heater to vaporize any liquid refrigerant in the compressor crankcase.
Start unit and check rotation of fans and compressors.
Scroll compressors will only compress in one rotational direction. Three phase compressors will rotate in either direction depending upon phasing of the power. Since there is a
Verification of proper direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized. Reverse rota- tion also results in an elevated sound level as well as substantially reduced current draw.
If opposite rotation is needed, disconnect and reverse any two leads of the three phase supply. Reconnect power and observe for correct rotation.
Observe unit operation and check for unusual noise or vibration.
REFRIGERANT CHARGES
Ref. Charge | 2 TON | 3 TON | 4 TON | 5 TON |
No. of Circuits | 1 | 1 | 1 | 1 |
Per Circuit (lb) | 7.625 | 8.125 | 11.188 | 10.938 |
The Air Conditioning section of this equipment is charged with
PRESSURE SWITCH SETTINGS |
| |
|
|
|
| ALL MODELS |
|
| High | Low |
Cut Out (PSIG) | 600 | 55 |
Cut In (PSIG) | 450 | 75 |
There is no negative impacts on durability caused by operating three phase Scroll compressors in the re- versed direction for a short period of time (less than one hour). However, after several minutes of operation the compressors internal protector will trip.
RECCOMENEDED REFRIGERANT LINE SIZES
UNIT SIZE | LESS THAN 60 LINEAR FEET | 60 - 150 LINEAR FEET | |||
LIQUID LINE | SUCTION LINE | LIQUID LINE | SUCTION LINE | ||
| |||||
2 TON | 5/16 | 5/8 | 3/8 | 3/4 | |
3 TON | 3/8 | 3/4 | 3/8 | 7/8 | |
4 TON | 3/8 | 7/8 | 1/2 | ||
5 TON | 3/8 | 1/2 | |||
8 TON | 2 X 3/8 | 2 X 7/8 | 2 X 3/8 | 2 X | |
10 TON | 2 X 3/8 | 2 X | 2 X 1/2 | 2 X | |
12 TON | 2 X 1/2 | 2 X | 2 X 1/2 | 2 X | |
15 TON | 2 X 1/2 | 2 X | 2 X 5/8 | 2 X |
NOTES: - Maximum Suction Lift 60 FT
-Maximum Liquid Line Rise 40 FT (measured from condensing unit level).
-Liquid Line Solenoid Valve required on systems over 100 linear feet.
-Suction Accumulator(s) required on systems over 125 linear feet.