VENT TERMINAL CLEARANCES

VENT TERMINAL CLEARANCES

Figure 3

A= Clearance above grade, verandah, porch, deck, or

H= *Not to be installed above a meter/regulator

[balcony (*12 inches (30cm) minimum]

assembly within 3 feet (90cm) horizontally from

B= Clearance to window or door that may be opened [*12

the center-line of the regulator

inches (30cm) minimum]

I= Clearance to service regulator vent outlet

C= Clearance to permanently closed window

[*6 feet

(1.8m) minimum]

[minimum 12 inches (30cm) recommended to

J= Clearance to non-mechanical air supply inlet to

prevent condensation on window]

building or the combustion air inlet to any

D= Vertical clearance to ventilated soffit located

other appliance [12 inches (30cm) minimum]

above the terminal within a horizontal

K= Clearance to a mechanical air supply inlet

distance of 2 feet (60cm) from the center-line

[*6 feet (1.8m) minimum]

of the terminal 24 inches ( 60cm) minimum

L= *** Clearance above paved side-walk or paved

E= Clearance to unventilated soffit

driveway located on public property

[18 inches (45cm) minimum]

[*7 feet

(2.1m) minimum]

F= Clearance to outside corner [12 inches minimum]

M= Clearance under verandah, porch, deck, or

G= Clearance to inside corner [`12 inches minimum]

balcony [*24 inches (60cm) minimum **]

***A vent shall not terminate directly above a sidewalk or paved driveway, which is located between two single family dwellings and serves both dwellings.

**Only permitted if verandah, porch, deck, or balcony, is fully open on a minimum of 2 sides beneath the floor

As specified in CGA B149 Installation Codes (1991) Note: Local Codes or Regulations may require different clearances