Troubleshooting Guide

Troubleshooting Guide

Problem

Possible Cause

 

Remedy

Failure to

1. No electrical power to

1. Check power

start or no

unit

 

 

air delivery

• Fuse blown

• Replace fuse

 

• Circuit breaker

• Reset breaker

 

tripped

 

 

 

2. Belt too loose or tight

2.

Adjust belt tension

 

3. Motor overheated

3. Determine cause of

 

 

 

overheating

 

• Belt too tight

• Adjust belt tension

 

• Blower bearings dry

• Grease blower

 

 

 

bearings

 

4. Motor locked

4.

Replace motor

 

 

 

Inadequate

1. Insufficient air exhaust

1. Open windows or

air delivery

 

 

doors to increase air

with cooler

 

 

flow

running

2. Belt too loose

2.

Adjust belt tension

 

 

 

or replace if needed

 

3. Pads plugged

3.

Clean pads

 

4. Insufficient water

4.

Clean distribution

 

flow over pads

 

system

 

 

 

Motor

1. Low voltage

1. Check voltage

cycles on

2. Excessive belt tension

2.

Adjust belt tension

and off

3. Fan shaft tight or

3.

Grease or replace

 

locked

 

bearings (Disconnect

 

 

 

unit)

 

4. Bearings dry

4. Grease bearings

 

5. Faulty motor

5.

Replace motor

Problem

Possible Cause

Remedy

Musty or

1. Stale or stagnate water

1. Drain pan and clean

unpleasant

in cooler

pads

odor

2. Pads not wetting

2. Check water

 

properly

distribution system

 

• Dist. tube holes

• Clean

 

clogged

 

 

• Pump not working

• Replace or clean

 

properly

pump (Unplug)

 

• Insufficient water

• Clean water

 

flow over pads

distribution system

 

 

 

Noisy

1. Bearings dry

1. Grease bearings

 

2. Loose parts

2. Tighten loose parts

 

 

 

Inadequate

1. Inadequate exhaust in

1. Open windows or

cooling

building

doors to increase air

 

 

flow

 

2. Pads not wet

2. Check water

 

 

distribution system

 

• Pads plugged

• Clean pads

 

• Dist. tube holes

• Clean

 

clogged

 

 

• Pump not working

• Replace or clean

 

properly

pump (Unplug)

 

 

 

Excessive

1. Inadequate exhaust

1. Open doors or

humidity

 

windows

in building

 

 

Limited Warranty

This warranty is extended to the original purchaser of an evaporative cooler installed and used under normal conditions. It does not cover damages incurred through accident, neglect, or abuse by the owner. We do not authorize any person or representative to assume for us any other or different liability in connection with this product.

Terms And Conditions Of Warranty

Lifetime Limited Coverage on water reservoir against any leakage due to defects in material. From date of purchase, if any original component part fails due to defect in material or factory workmanship only, we will provide the replacement part as follows:

One year on the cabinet components.

Two years on the evaporative media.

Exclusions From The Warranty

We are not responsible for any incidental or consequential damage resulting from any malfunction.

We are not responsible for any damage received from the use of water softeners, chemicals, descale material, plastic wrap, or if a motor of a higher horsepower than what is shown on the serial plate is used in the unit.

We are not responsible for the cost of service calls to diagnose cause of trouble, or labor charge to repair and/or replace parts.

How To Obtain Service Under This Warranty

Contact the Dealer where you purchased the evaporative cooler. If for any reason you are not satisfied with the response from the dealer, contact the Customer Service Department: 5800 Murray Street, Little Rock, Arkansas 72209. 1-800-643-8341. E-mail: info@championcooler.com, Web: www.championcooler.com.

This limited warranty applies to original purchaser only

4

110497

Page 4
Image 4
Essick Air FAD248 Troubleshooting Guide, Limited Warranty, Problem, Possible Cause, Remedy, Exclusions From The Warranty