TOOLS NEEDED FOR INSTALLATION
• Saber Saw or Jig Saw
• Drill
• 1 1/4" Wood Drill Bit
• Pliers
• Phillips Screwdriver
• Wire Stripper or Utility Knife
• Metal Snips
• Measuring Tape or Ruler
• Level
• Pencil
• Caulking Gun
• Duct Tape
PLAN THE DUCTWORK
The Velvet slideout rangehood is designed to offer wide flexibility of installations. The rangehood can be ducted through a 6" round vent. The unit can also be installed in a recirculating configuration. The unit comes standard in the top venting position. FIGURE 3 shows recirculating installation.
The Velvet requires 6" round ductwork. To ensure that the blower performs to its highest possible capacity, ductwork should be as short and straight as pos- silbe.
PARTS SUPPLIED FOR INSTALLATION
• 1 Backdraft Damper
• 1 Literature Package
PARTS NEEDED FOR INSTALLATION
• 2 Conduit Connectors
• Power Supply Cable
• 1 Wall or Roof Cap
• All Metal Ductwork
OPTIONAL ACCESSORIES AVAILABLE
• Charcoal Filters
For
The ductrun should not exceed 35 feet if ducted with the required minimum of 6" round duct. Cal- culate the length of the ductwork by adding the equivalent feet in FIGUREA for each piece of duct in the system An example is given in FIGURE B.
For best results, use no more than three 90° elbows. Make sure that there is a minimum of 24" of straight duct between elbows if more than one is used. Do not install two elbows together. If you must elbow right away, do it as far away from the hood's exhaust opening as possible.
45˚ Elbow | 3.0 feet |
90˚ Elbow | 5.0 feet |
90˚ Flat Elbow | 12.0 feet |
Wall Cap | 0.0 feet |
FIGURE A |
|
|
|
|
|
9 Feet Straight Duct | 9.0 feet |
2 - 90˚ Elbows | 10.0 feet |
Wall Cap | 0.0 feet |
Total System | 19.0 feet |
FIGURE B |
|
|
|
VERTICAL DUCTING
FIGURE 1
HORIZONTAL
DUCTING
FIGURE 2
For direct rear venting (FIGURE 2), you must change the blower position. Remove the 12 screws that hold the metal housing to the rangehood body. Remove the 4 screws that hold the blower housing to the metal housing. Rotate the blower 90 degrees toward the back and then flip it over 180 degrees. Be sure that the power supply cable is properly positioned. Replace all screws, making sure that they are firmly fastened.
RECIRCULATING INSTALLATIONS
For recirculating installations (FIGURE 3), Charcoal Filters are necessary. Open the comfort panel by turning the knobs to the right, slide open the glass visor, and remove the grease filters and set aside. Attach one charcoal filter to each end of the blower. Each charcoal filter attaches to the of the side of the blower. Rotate the filter clockwise to install and counterclockwise to remove (FIGURE 3A). Replace the grease filters and reattach the comfort panel. Some ductwork must be installed to exhaust the rangehood back into the kitchen, either at the top of the cabinet or at the face of the soffit. Using a plastic vent grate to cover the duct opening. This duct work must not terminate into a dead air space.
| ceiling | soffit | ceiling |
|
|
| vent grate |
| vent grate |
|
|
cabinet | 6” round | cabinet | 6” round |
|
| ||
| duct |
| duct |
| hood |
| hood |
|
| FIGURE 3 |
|
FIGURE 3A
Version 07/08 - Page 5