SG RACKMOUNT EXTENDED BATTERY BANK SELECTION GUIDE
FOR 1KVA MODELS
BATTERY OPTION | ||||||
MODEL | ||||||
|
|
|
|
| ||
BATTERIES | 7AH x 3 | 7AH x 6 | (7AH x 6) x 2 | (7AH x 6) x 3 | (7AH x 6) x 4 | |
BATTERIES IN UPS | Batteries & UPS | 7AH x 3 | 7AH x 3 | 7AH x 3 | 7AH x 3 | |
in same case | ||||||
|
|
|
|
| ||
# OF BATTERY CASES | UPS | 1 | 2 | 3 | 4 | |
RUN TIME @ 100W | 54 Min. | 220 min. | 400 Min. | 590 Min. | 760 Min. | |
RUN TIME @ 200W | 25 Min. | 100 Min. | 190 Min. | 280 Min. | 380 Min. | |
RUN TIME @ 400W | 11.5 Min. | 45 Min. | 90 Min. | 140 Min. | 190 Min. | |
RUN TIME @ 700W | 7 Min. | 24 Min. | 45 Min. | 72 Min. | 100 Min. | |
CHARGER TYPE | 800ma/41.1Vdc |
| Contact Factory |
| ||
NO. OF CHARGERS | 1 (UPS) | 0 | 0 | 0 | 0 |
FOR 2KVA MODELS
BATTERY OPTION | |||||||
MODEL | |||||||
|
|
|
|
|
| ||
BATTERIES | 7AH x 6 | (7AH x 6) x 2 | (7AH x 6) x 3 | (7AH x 6) x 4 | (7AH x 6) x 5 | ||
BATTERIES IN UPS |
|
| NONE |
|
| ||
# OF CASES | 1 | 2 |
| 3 | 4 | 5 | |
Comes with UPS |
| ||||||
|
|
|
|
|
| ||
RUN TIME @ 300W | 40 Min. | 92 Min. | 112 Min. | 225 Min. | 300 Min. | ||
RUN TIME @ 500W | 24 Min. | 55 Min. | 95 | Min. | 135 Min. | 180 Min. | |
RUN TIME @ 700W | 17 Min. | 40 Min. | 70 | Min. | 100 Min. | 140 Min. | |
RUN TIME @ 1000W | 11 Min. | 25 Min. | 42 | Min. | 60 Min. | 80 Min. | |
RUN TIME @ 1400W | 7 Min. | 16 Min. | 26 | Min. | 38 Min. | 62 Min. | |
CHARGER TYPE | Inside UPS |
|
| Contact Factory |
| ||
NO. OF CHARGERS | 0 | 0 |
| 0 | 0 | 0 |
FOR 3KVA MODELS
| BATTERY OPTION | |||||
| MODEL | |||||
|
|
|
|
|
| |
| BATTERIES | 7AH x 8 | (7AH x 8) x 2 | (7AH x 8) x 3 | (7AH x 8) x 4 | (7AH x 8) x 5 |
| BATTERIES IN UPS |
|
| NONE |
|
|
| CASE |
| 2 | 3 | 4 | 5 |
| Comes with UPS | |||||
|
|
|
|
|
| |
| RUN TIME @ 500W | 33 Min. | 96 Min. | 160 Min. | 230 Min. | 320 Min |
| RUN TIME @ 1000W | 17.5 Min. | 50 Min. | 84 Min. | 120 Min. | 165 Min. |
| RUN TIME @ 1500W | 10 Min. | 30 Min. | 51 Min. | 77 Min. | 105 Min. |
| RUN TIME @ 2100W | 6 Min. | 19 Min. | 35 Min. | 51 Min. | 70 Min. |
| CHARGER TYPE | Comes with UPS |
| Contact Factory |
| |
| NO. OF CHARGERS | Inside UPS | 0 | 0 | 0 | 0 |
NOTE: The backup times stated are for reference only. Backup time may vary due to the type of load, battery | age or condition, | |||||
| environmental conditions, etc. |
|
|
|
|