Typical Falcon Opto-coupler Interface Card

 

PIN ASSIGNMENT FOR THE FALCON

 

UA88373 OPTO-COUPLER OPTION BOARD

 

(no-bypass signal)

 

 

PIN

DESCRIPTION

1

Not Used

2

Utility Loss (N.O.) (Closes upon utility loss)

3

Utility Loss (N.C.) (Opens upon utility loss)

4

Common for pins 2, 3 & 5

5

Low Battery (N.O.) (Closes at low battery)

6

Remote Shutdown

 

Applying a +5-+12Vdc voltage level for >500ms,

 

while the UPS is on battery will shutdown the

 

UPS

7

Not Used

8

Not Used

9

Not Used

OPTO Board Internal Circuitry

(E)

(B)

Utility Loss

(A)

DB-9

(C)

To CPU

(A)

6

 

(K)

 

2

 

7

 

 

8 3

4

5

Alarm Signal

Low Battery Signal

17