5.For all 1kVA &
6.Connect the power cord(s) for the equipment to be protected to the UPS output receptacles.
7.For all 2 & 3kVA models remove the two screws securing the battery connector cover plate on the UPS module rear panel. Next remove the two screws securing the upper battery connector cover plate located on the battery module rear panel. Connect one end of the battery interconnect cable to the mating battery connector on the UPS. On the primary battery bank remove the battery fuse and connect the other end of the battery cable to the upper battery connector (located on the battery bank rear panel). Depress and hold the precharge pudhbutton while reinstalling the battery fuse
8.If additional extended battery modules are to be installed, perform the following:
a.Perform the preperation outlined in preceding paragraphs 3a, 3b, abd 3c.
b.Connect the supplied battery interconnect cable(s). Connect one end of the battery interconnect cable to the mating lower battery connector on the first battery module. On extended battery bank, depress the
BATTERY MODULE INTERCONNECT WIRING
UPS |
| UPS Battery |
|
| Connector |
|
|
|
Standard 2 & 3Kva battery Module or Optional 1Kva extended battery module
Battery
Interconnect
Cable
Battery
Interconnect
Cable
Optional extended battery module
Optional extended battery module
Battery
Interconnect
Typical battery fuse
Typical Battery/UPS |
| Lower cover |
button |
| plate shown |
|
|
|
|
|
|
6