XIII. Self Test
Main PCB
To initiate the
a)Turn on the ac. supply to the
b)Press and hold the Operation / Filter reset button for 6 seconds after which you can hear 2 beep sound to indicate activation of
(Note : When press and hold for 3 seconds, a single beep will be heard. Keep on holding for another 3 seconds to achieve the total 6 seconds requirement to activate the
Observe the following events.
iall output devices are turned off
iiEEPROM is tested. If EEPROM is faulty, buzzer will sound for 3s
iiigreen, yellow & red LEDs are turned on.
iv1s later, the
v1s later, compressor is turned on
vi1s later, outdoor fan is turned on
vii1s later, indoor fan runs at low speed for 3s
viiiFollowing, the indoor fan runs at medium speed for 3s
ixFollowing, the indoor fan runs at high speed
x3s later, the vane moves to down position, taking 3.42s & stays for 2s
xiThe vane moves to home position, taking 1.47s and stays for 2s
xiiThe vane moves to middle position, taking 1.39s and stays for 2s
xiiiThe vane moves to angle position, taking 0.565s & stays for 2s.
xivThe vane moves to home position again, takes 1.96s & stays for 2s.
xvAll output devices are turned OFF.
For normal operation, power off the system and turn on the system again to cause a power on reset.
XIV. Memory Backup of Settings
Once the setting of the unit changed, it will be stored into the EEPROM immediately. After current restoration due to power source supply breakdown, the unit commences operation using all the settings at the time of the breakdown. However, all timing related fuction will be invalid. The unit will be randomly start with 3 minutes delay for compressor protection.