Diagram B
CONNECTING POWER VENTER TO APPLIANCE
Venting system should be installed and supported in accordance with the National Flue Gas Code A.N.S.I.Z223.1, or in accordance with any local codes. A vent pipe connector shall be supported for the design and weight of the material employed, to maintain clearances, prevent physical damage and separation of joints. A vent pipe increaser or reducer may be required for connecting the power venter to the vent system. If needed, place the reducer close to the power venter. Smaller vent pipe sizes than a
If mounting venting system near combustible materials, refer to Diagram B for allowable installation clearances. Clearances are based on an installation using single wall galvanized steel vent pipe. For metal thickness of galvanized steel pipe connectors, refer to NFPA 211 or NFPA 54 Standards for guidelines. If manufactured double wall vent pipe is required or used for the installation, clearance should be based on the vent pipes rated clearance. Always check local code requirements for code restrictions.
Route the vent pipe from the appliance to the power venter using a minimum number of elbows as possible. The horizontal section of the vent pipe should have a slight upward slope from the appliance to the power venter. For clearances to combustible materials, multiple appliance venting and other installation requirements, refer to the National Fuel Gas Code A.N.S.I.Z223.1, and/or any applicable local codes or appliance manufacturer's installation instructions.
INSTALLATION USING SINGLE WALL VENT PIPE (See Table 3)
Table 3
INSTALLATION CLEARANCE WITH SINGLE WALL VENT PIPE
DOUBLE PIPE SYSTEM |
| SINGLE PIPE SYSTEM |
| |||
Allowable inlet | Allowable inlet |
| Allowable inlet | Allowable inlet |
| |
temperature | Clearance | temperature | Clearance | |||
temperature | temperature | |||||
SWG Stainless | (A) | SWG Stainless | (B) | |||
SWG/SWGII | SWG/SWGII | |||||
Steel |
| Steel |
| |||
|
|
|
| |||
400°F or less | 400°F or less | 1/2” | 400°F or less | 400°F or less | 3” | |
minimum | minimum | |||||
|
|
|
| |||
400°F to | 400°F to 550°F | 1” | 400°F to | 400°F to 550°F | 4” | |
650°F US/575°F CA | minimum | 650°F US/575°F CA | minimum | |||
|
| |||||
400°F to |
| 1/2” | 400°F to |
| 3” | |
400°F to 550°F | minimum | 400°F to 550°F | minimum | |||
650°F US/575°F CA | with sheet | 650°F US/575°F CA | with sheet | |||
|
| |||||
|
| metal liner |
|
| metal liner | |
Use a PEK series extension kit or follow installation method below for a double pipe system. To |
| |||||
install an outer pipe extension to the SWG power venter, the end pipe cover on the power venter |
| |||||
must be removed. Then, cut a |
| |||||
the power venter. (See Figure 5) This allows clearance for the adjustment damper. Install the |
| |||||
needed pipe extensions and terminate the outer pipe extension with the end pipe cover (see |
| |||||
Diagram B). The table above shows minimum allowable clearances when using single or double |
| |||||
pipe systems. When the outer pipe is extended over the inner pipe, use the double pipe | Figure 5 | |||||
guidelines when determining clearances. Figure 6 shows how the airflow pattern through an | ||||||
SWG reduces the required clearances to combustibles. NOTE: Vent pipe joints should be |
| |||||
secured with at least (3) three sheet metal screws. |
|
|
|
Page 6