Field Controls SWG Stainless, SWGII Diagram B, INSTALLATION USING SINGLE WALL VENT PIPESee Table

Models: SWGII SWG SWG Stainless

1 12
Download 12 pages 44.26 Kb
Page 6
Image 6
Diagram B

Diagram B

CONNECTING POWER VENTER TO APPLIANCE

Venting system should be installed and supported in accordance with the National Flue Gas Code A.N.S.I.Z223.1, or in accordance with any local codes. A vent pipe connector shall be supported for the design and weight of the material employed, to maintain clearances, prevent physical damage and separation of joints. A vent pipe increaser or reducer may be required for connecting the power venter to the vent system. If needed, place the reducer close to the power venter. Smaller vent pipe sizes than a chimney-vented system may be used for the vent system.

If mounting venting system near combustible materials, refer to Diagram B for allowable installation clearances. Clearances are based on an installation using single wall galvanized steel vent pipe. For metal thickness of galvanized steel pipe connectors, refer to NFPA 211 or NFPA 54 Standards for guidelines. If manufactured double wall vent pipe is required or used for the installation, clearance should be based on the vent pipes rated clearance. Always check local code requirements for code restrictions.

Route the vent pipe from the appliance to the power venter using a minimum number of elbows as possible. The horizontal section of the vent pipe should have a slight upward slope from the appliance to the power venter. For clearances to combustible materials, multiple appliance venting and other installation requirements, refer to the National Fuel Gas Code A.N.S.I.Z223.1, and/or any applicable local codes or appliance manufacturer's installation instructions.

INSTALLATION USING SINGLE WALL VENT PIPE (See Table 3)

Table 3

INSTALLATION CLEARANCE WITH SINGLE WALL VENT PIPE

DOUBLE PIPE SYSTEM

 

SINGLE PIPE SYSTEM

 

Allowable inlet

Allowable inlet

 

Allowable inlet

Allowable inlet

 

temperature

Clearance

temperature

Clearance

temperature

temperature

SWG Stainless

(A)

SWG Stainless

(B)

SWG/SWGII

SWG/SWGII

Steel

 

Steel

 

 

 

 

 

400°F or less

400°F or less

1/2”

400°F or less

400°F or less

3”

minimum

minimum

 

 

 

 

400°F to

400°F to 550°F

1”

400°F to

400°F to 550°F

4”

650°F US/575°F CA

minimum

650°F US/575°F CA

minimum

 

 

400°F to

 

1/2”

400°F to

 

3”

400°F to 550°F

minimum

400°F to 550°F

minimum

650°F US/575°F CA

with sheet

650°F US/575°F CA

with sheet

 

 

 

 

metal liner

 

 

metal liner

Use a PEK series extension kit or follow installation method below for a double pipe system. To

 

install an outer pipe extension to the SWG power venter, the end pipe cover on the power venter

 

must be removed. Then, cut a 1-inch square notch into the vent pipe extension before attaching

 

the power venter. (See Figure 5) This allows clearance for the adjustment damper. Install the

 

needed pipe extensions and terminate the outer pipe extension with the end pipe cover (see

 

Diagram B). The table above shows minimum allowable clearances when using single or double

 

pipe systems. When the outer pipe is extended over the inner pipe, use the double pipe

Figure 5

guidelines when determining clearances. Figure 6 shows how the airflow pattern through an

SWG reduces the required clearances to combustibles. NOTE: Vent pipe joints should be

 

secured with at least (3) three sheet metal screws.

 

 

 

Page 6

Page 6
Image 6
Field Controls SWG Stainless, SWGII Diagram B, INSTALLATION USING SINGLE WALL VENT PIPESee Table, Double Pipe System