Field Controls UV-16/24 installation instructions SIZING AND SELECTING UNITS See chart below

Models: UV-16/24

1 8
Download 8 pages 52.39 Kb
Page 3
Image 3
SIZING AND SELECTING UNITS

SIZING AND SELECTING UNITS

See chart below:

Square Footage

UV-Aire

Volts

Watts

Amps

Hz

(For ducts at least 16" wide)

Up to 2000

1

24

23

1.3

60

4000

2

24

46

2.6

60

Notes:

For applications with multiple systems, we recommend one unit per system.

For larger applications, multiple units are recommended.

Contact technical support at 1-252-522-3031 for sizing.

Each unit will require its own transformer.

Figure 1

INSTALLATION

 

1.

Locate a suitable location for the unit downstream from the 'A' coil in

 

 

the supply plenum or in the return plenum; preferably downstream from

 

 

the air filter. For optimum "cleaning" effect on the 'A' coil, mount the

 

 

unit in the supply plenum as close as possible to the 'A' coil.

 

 

(See Figure 1)

 

CAUTION: Investigate and determine the location of the A coil prior to

 

drilling holes in duct for mounting unit.

 

NOTE: For duct board installation, refer to enclosed bagged assembly

 

containing mounting plate and instructions.

Figure 2

2.

Apply supplied mounting template to air duct in either

 

 

a vertical or horizontal position. (See Figure 2) Leave

 

 

template mounted to duct for future reference.

 

3.

Drill 18" diameter mounting holes at positions indicated

 

 

on template. (See Figure 3)

 

4.

Cut out the large opening (1-12" hole) on the template.

 

 

(See Figure 3)

 

5.

Using a 14" to 12" drill bit, drill a viewport hole as

 

 

indicated on the template. (Figure 3)

 

6.

Optional Light Shield: The light shield may be mounted

 

 

at virtually any angle. However, when deciding on a

 

 

suitable location, the mounting screw head can not be in

 

 

the shaded area of template. (See Figure 4 to view areas

 

 

to avoid.)

Figure 3

 

 

Figure 4

Head of mounting screw CANNOT be

located in shaded area.

WARNING: Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or blindness. Never operate the UV-AireAir Purifying System out of the plenum. Avoid touching the glass portion of the lamp with your hands.

page 3

Page 3