REPLACEMENT PROCEDURE

WARNING: Disconnect power to the transfomer before starting replacement procedure.

NOTE: Wear disposable, non-absorbent protective gloves prior to replacement procedure in case of accidental breakage of glass.

1.Rotate the UV-Aire ballast assembly counter-clockwise until it stops. (See Figure 9)

2.Remove the ballast assembly and lamp from the mounting base. (See Figure 7)

3.

Remove the lamp from the lamp socket. (See Figure 6)

 

Figure 9

 

4.

Install the replacement lamp into lamp socket. Do not handle the lamp with

 

 

 

 

 

bare hands. Oils on the hands tend to reduce lamp intensity.

 

 

5.

Wipe off the glass with the supplied alcohol wipe.

 

 

6.

Position the ballast assembly power cord 90° to the viewport hole on the

 

 

 

mounting base. (See Figure 9)

 

 

7.

Slide the lamp through the hole in the mounting base. (See Figure 7)

 

 

8.

Press the ballast against the mounting base. Rotate the ballast assembly

 

 

 

clockwise until it stops and is locked in place. (See Figure 10)

 

 

9.

After assembly is firmly in place, reconnect power to transformer, and plug

 

 

 

Figure 10

 

the power supply cord back into the standard electrical outlet. Check lamp

 

 

operation by looking through the viewport hole. A blue glow should be seen in the duct.

 

10.After replacing the lamp, make sure to install the Lamp Replacement Label. Print the date on the label and apply to the side of ballast assembly.

NOTE: If blue light leaks through any portion of plenum and/or around mounting plate, unplug power supply cord immediately and seal affected areas and/or rotate ballast and repeat step #8.

11.UV lamps contain a small amount of mercury, like a typical fluorescent lamp. Check with your local waste management authority for local disposal or recycling requirements. According to the EPA's Universal Waste Rule, these types of lamps may be disposed of into household waste.

WARNING: Never touch broken lamp or internal contents of lamp. The lamp contains mercury.

NOTE: In case of accidental exposure to internal contents of lamp, wash hands and any other affected skin area with mild detergent. Remove affected clothing immediately. If skin surface is pierced, seek medical attention immediately.

WARNING: Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or blindness. Never operate the UV-AireAir Purifying System out of the plenum. Avoid touching the glass portion of the lamp with your hands.

page 6

Page 6
Image 6
Field Controls UV-16/24 installation instructions Replacement Procedure

UV-16/24 specifications

The Field Controls UV-16/24 is an advanced ultraviolet (UV) air purification system designed to improve indoor air quality in residential and commercial settings. The unit is particularly effective in combatting airborne pathogens, mold spores, and volatile organic compounds (VOCs), making it an essential addition to HVAC systems.

One of the standout features of the UV-16/24 is its dual UV-C lamp configuration. This design maximizes germicidal efficacy by offering thorough exposure to UV light, effectively neutralizing microorganisms present in the air as it circulates through the HVAC system. The 16- or 24-inch length of the lamps also optimizes coverage for various system sizes.

The technology behind the UV-16/24 ensures that the units operate efficiently while minimizing energy consumption. The implementation of high-output UV lamps allows for maximum disinfection within a compact form factor. The system boasts easy installation within existing HVAC frameworks, which makes it suitable for both new builds and retrofitting older systems.

Another notable characteristic of the UV-16/24 is its durable construction, designed to withstand the rigors of continuous operation. The unit features corrosion-resistant components and housing, ensuring longevity and reliability even in varying environmental conditions.

Safety is prioritized in the UV-16/24, featuring automatic shutoff capabilities when the housing is opened for maintenance. This ensures that users and technicians are not exposed to harmful UV rays during lamp replacement or service.

The Field Controls UV-16/24 operates quietly, making it a desirable option for residential settings where noise can be a concern. By utilizing UV-C technology, it does not rely on chemicals, thus contributing to a healthier indoor environment without introducing harmful substances.

Additionally, the system is designed with easy maintenance in mind. The replacement lamps are both user-friendly and readily available, simplifying the upkeep process and ensuring that optimal operation is maintained over time.

In conclusion, the Field Controls UV-16/24 presents a robust solution for enhancing indoor air quality. With its dual UV-C lamp technology, energy efficiency, durable build, safety features, and low maintenance requirements, it stands out as a reliable tool in the ongoing effort to create healthier indoor spaces. Whether for a home or commercial application, the UV-16/24 is a proactive choice for anyone looking to improve their air quality.