3.Hardware Connections

The ProtoNode is connected to the UPS as shown in connection drawing. Configure the TIC UPS according to manufacturer’s instructions.

Toshiba UPS

 

8917-03 WIRE LIST

DB9M

FUNCTION

FROM

TO

COLOUR

 

Rx

RJ45-01

DB9M-02

GREY

 

GND

RJ45-04

DB9M-05

GREEN

 

Tx

RJ45-08

DB9M-03

BLUE

 

 

8917-02 WIRE LIST

 

 

 

FUNCTION

FROM

TO

COLOUR

 

 

Rx

RJ45-01

DB9F-03

WHITE

 

 

GND

RJ45-04

DB9F-05

GREEN

 

 

Tx

RJ45-08

DB9F-02

BLUE

 

 

 

 

 

 

 

(408)-262-2299

 

 

 

 

PROTONODE

 

 

 

 

DB9F

TOSHIBA UPS

 

 

 

 

CONNECTION DIAGRAM

 

 

 

 

 

PROTONODE

 

BASE NAME:

DATE: 10/10/07

 

 

 

 

FILE NAME: FS-8700-124

BY: MC

3.1.Hardware Connection Tips / Hints

The RTS/DTS signals are not used by the driver. Make sure they are not connected and do not enable them in the configuration file.

The cable must be a NULL modem cable, i.e. the TX must be connected to the other connector’s RX.