Appendix A.1.2. ALARM command:

Stored in bits, make sure array’s length is 24 and its type is bits.

Bit #

Description

Bit 23:

Not used

Bit 22:

1

Bit 21:

Low battery voltage

Bit 20:

Battery replacement alarm

Bit 19:

Parallel running mode

Bit 18:

0

Bit 17:

0

Bit 16:

UPS lifetime alarm

Bit 15:

Not used

Bit 14:

1

Bit 13:

Asynchronous operation

Bit 12:

Ambient overheat

Bit 11:

Overload accumulation started

Bit 10:

0

Bit 9:

0

Bit 8:

0

Bit 7:

Not used

Bit 6:

1

Bit 5:

Countdown started for shutdown

Bit 4:

0

Bit 3:

0

Bit 2:

0

Bit 1:

0

Bit 0:

0

Appendix A.1.3. STATUS command:

Stored in bits, make sure array’s length is 8 and its type is bits.

Bit #

Description

Bit 7:

Not used

Bit 6:

1

Bit 5:

UPS fault detected

Bit 4:

Input voltage out of spec

Bit 3:

Low battery voltage detected

Bit 2:

UPS output from bypass

Bit 1:

UPS output from inverter

Bit 0:

UPS input and output voltage sync